Magnum Energy ME-PT2 Instruction Sheet Download Page 2

ME-PT2 Instruction Sheet

© 2014 Magnum Energy, Inc.

Figure 1, ME-PT2 to ME-AGS-N Installation

Dometic Comfort Control Center™

ME-PT2 can be used in conjunction with the Dometic / Duo-Therm kit 

(3109226.005) 

and 

Dometic Comfort Control Center™ to connect the t-stat output of the A/C directly to the AGS. 
This allows the AGS to start on demand from the A/C for either heat (heat pump only) or cool.
1. Connect the two wires from the ME-PT2 adapter to the Duo-Therm per the kit instructions. 
     Make sure to set the #8 DIP switch on the Duo-Therm control box per instructions.
2. Follow Comfort Control Center™ instructions for proper zones, heat, cool and AGS settings.
3. The ME-AGS-N will now start on demand from the Comfort Control Center™.

External

Maintain Switch

External

Momentary Switch

PT2-AGS

To Network port on 

Magnum inverter

ME-AGS-N

options

ON

OFF

Air Conditioner 

(wire to electronic 

  control box)

ME-RC

 One time push 

(or close): gen runs 
for duration of run 
time cycle, then stops.

ME-ARC

 Press switch: 

gen runs for 2 mins, 
then stops.

ME-ARC

 Switch set 

to ON: gen runs until 
switch set to OFF. 
Switch set to OFF: 
gen runs for 2 mins, 
then stops.

ME-RC

 Switch set to 

ON: gen runs until 
switch set to OFF. 
Switch set to OFF: gen 
runs for remaining 
duration of run time 
cycle, and then stops.

ME-ARC

A. 

Using a momentary type switch:

 Pressing the switch causes the generator 

to run for two minutes, and then stop.

B. 

Using  a  maintain  type  switch:

  If  the  switch  is  set  to  ON,  the  generator 

continues to run until the switch is set to OFF. Once the switch is set to OFF, 
the generator will run for two minutes, and then stop.

ME-PT2 Instruction Sheet

© 2014 Magnum Energy, Inc. 

3

Installation/Setup – ME-AGS-S (Standalone Version)

The  following  pertains  to  the  ME-PT2  when  connected  to  the  ME-AGS-S 
(Standalone Version) controller.

Info:

 Other than the specifi c installation and setup instructions listed 

below,  refer  to  the  ME-AGS-S  Owner’s  Manual  (PN:  64-0004)  for 
installation, setup, and operation of the ME-AGS-S.

Installation

To prepare the ME-AGS-S remote switch:

1.  Find the temperature sensor behind the remote switch’s front plate. It is a 

small reddish looking device close to the metal front plate (see Figure 2).

2.  Use a pair of small wire cutters to cut open one side of the temperature 

sensor wire (see Figure 3). Ensure the cut ends are not able to touch.

To install the ME-PT2 (refer to the steps below and Figure 4):

1.  Plug a 6-conductor phone splitter into the REMOTE (purple) port on the 

ME-AGS-S controller.

2.  Plug  the  ME-PT2  adapter  into  one  of  the  phone  splitter’s  ports,  and 

then plug the remote switch—using its communications cable—into the 
phone splitter’s other port.

3.  Connect  the  two  white  wires  on  the  ME-PT2  pigtail  adapter  to  a  two-

contact external switching device (i.e., switch).

Temperature 

Sensor

Temperature 

Sensor

(cut open)

Figure 2, Locating Sensor

Figure 3, Sensor Cut Open

Setup

1.  On the ME-AGS-S, turn the START TEMP F adjustment clockwise to any 

temperature position (

DO NOT

 turn counterclockwise to OFF position).

2.  Press the remote switch on the ME-AGS-S to the up (ENABLE) position.

ME-PT2 to ME-AGS-S Operation

The type of external switch (i.e., “maintain” or “momentary”) connected to 
the ME-PT2 adapter determines how long the generator can run.

A. 

Using a 

momentary type switch:

 

Pressing the switch causes the generator 

to run for the duration of the RUN TIME HOURS period, and then stop.

B. 

Using a 

maintain type switch:

 

If the switch is set to OFF, the generator 

stays off. If the switch is set to ON, the generator runs until the switch is set 
to OFF. Once the switch is set to OFF, the generator will not stop until the 
current RUN TIME HOURS cycle has been satisfi ed.

Reviews: