Magnum Energy ME-PT1 Instruction Sheet Download Page 3

ME-PT1 Instruction Sheet

© 2014 Magnum Energy, Inc. 

3

Installation/Setup – ME-AGS-S (Standalone Version)

The following pertains to the ME-PT1 when connected to the ME-AGS-S 

(Standalone Version) controller.

Info: Other than the specifi c installation and setup instructions 

listed below, refer to the ME-AGS-S Owner’s Manual (64-0004) for 

installation, setup, and operation of the ME-AGS-S.

Installation

To prepare the ME-AGS-S remote switch:
1.  Find the temperature sensor behind the remote switch’s front plate. It is a 

small reddish looking device close to the metal front plate (see Figure 2).

2.  Use a pair of small wire cutters to cut open one side of the temperature 

sensor wire (see Figure 3). Ensure the cut ends are not able to touch.

To install the ME-PT1 (refer to the steps below and Figure 4):
1.  Plug a 6-conductor phone splitter into the REMOTE (purple) port on the 

ME-AGS-S controller.

2.  Plug the ME-PT1 adapter into one of the phone splitter’s ports, and 

then plug the remote switch—using its communications cable—into the 

phone splitter’s other port.

3.  Connect the red wire on the ME-PT1 adapter to a +12-volt DC external 

switching device (i.e., switch).

Temperature 

Sensor

Temperature 

Sensor

(cut open)

Figure 2, Locating Sensor

Figure 3, Sensor Cut Open

Setup

1.  On the ME-AGS-S, turn the START TEMP F adjustment clockwise to any 

temperature position (DO NOT turn counterclockwise to OFF position).

2.  Press the remote switch on the ME-AGS-S to the up (ENABLE) position.

ME-PT1 to ME-AGS-S Operation

The type of external switch (i.e., “maintain” or “momentary”) connected to 

the ME-PT1 adapter determines how long the generator can run.
A. Using a 

momentary type switch: 

Pressing the switch causes the generator 

to run for the duration of the RUN TIME HOURS period, and then stop.
B. Using a 

maintain type switch: 

If the switch is set to OFF, the generator 

stays off. If the switch is set to ON, the generator runs until the switch is set 

to OFF. Once the switch is set to OFF, the generator will not stop until the 

current RUN TIME HOURS cycle has been satisfi ed.

Summary of Contents for ME-PT1

Page 1: ...ion To install the ME PT1 refer to Figure 1 and the steps below 1 Connect the red wire on the ME PT1 adapter to a 12 volt DC external switching device i e switch 2 Plug the ME PT1 adapter into the REMOTE purple port on the ME AGS N Info The remote temperature sensor that comes with the ME AGS N normally plugged into the AGS s REMOTE port is not used when a ME PT1 is connected Setup When using the ...

Page 2: ...ion of run time cycle and then stops options PT1 AGS To Network port on Magnum inverter All grounds must be bonded together to ensure the ME PT1 works correctly GEN connection provides 12VDC from Zone Control Box when gen needs to start GEN connection GREEN GND WHITE L2 BLACK L1 ZONE CONTROL BOX 115 VAC IN 9 PIN PLUG TO UPPER UNIT FREEZE ROOM HEAT SHED COOL SHED TO USE WITH LOAD SHED DEVICE REMOVE...

Page 3: ... the phone splitter s ports and then plug the remote switch using its communications cable into the phone splitter s other port 3 Connect the red wire on the ME PT1 adapter to a 12 volt DC external switching device i e switch Temperature Sensor Temperature Sensor cut open Figure 2 Locating Sensor Figure 3 Sensor Cut Open Setup 1 On the ME AGS S turn the START TEMP F adjustment clockwise to any tem...

Page 4: ... current RUN TIME HOURS cycle has been satisfied options GEN connection provides 12VDC from Zone Control Box when gen needs to start GEN connection GREEN GND WHITE L2 BLACK L1 ZONE CONTROL BOX 115VAC IN 9 PIN PLUG TO UPPER UNIT FREEZE ROOM HEAT SHED COOL SHED TO USE WITH LOAD SHED DEVICE REMOVE JUMPER AND CONNECT TO N C CONTATCT ROOM SENSOR FREEZE SENSOR PT1 AGS Phone Splitter 6 conductor ME AGS S...

Reviews: