7.0 Using an AGS Module
82
© 2012 Magnum Energy, Inc.
To manually stop the generator:
1. Press the CTRL button.
2. Turn the SELECT knob to the
03 Gen Control
menu.
3. Press the SELECT knob. The
Set Gen Control
menu displays with an arrow
to the right of the current setting.
4. Turn the SELECT knob to the
OFF
setting.
5. Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen. The generator should stop at this time.
If the generator does not stop as expected, refer to Section 7.8 “ME-AGS-N
Remote Troubleshooting” in this manual.
To manually start the generator and have it automatically stop:
1. Press the CTRL button.
2. Turn the SELECT knob to the
03 Gen Control
menu.
3. Press the SELECT knob. The
Set Gen Control
menu displays with an arrow
to the right of the current setting.
4. Turn the SELECT knob to the
ON
setting.
5. Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen. The generator should start at this time.
Once the generator is running, rotate the SELECT knob to
AUTO
(under the
03 Gen Control
menu), and then press the SELECT knob to select this setting.
If the generator does not start or stop as expected, refer to Section 7.8 “ME-
AGS-N Remote Troubleshooting” in this manual.
Note:
When the generator is manually started, but then changed to autos-
top, the
SETUP: 04A Gen Run VDC
settings are used to determine when the
generator will autostop. If the
SETUP: 04A Gen Run VDC
is set to
OFF
, the
Start/Stop Volts Delay
and
Stop Gen Volts
values that were entered prior to
selecting
OFF
will still be used to autostop the generator.