© 2016 Sensata Technologies
22
Setup
ON
4
3
2
1
RY1
(N.O.)
RY2
(N.O.)
T1
T2
T3
GEN RUN PD.
T3
RY1
(N.O.)
T1
T2
GEN RUN PD.
RY2
(N.O.)
RY3
(N.O.)
T1
T2
GEN RUN PD.
Portable
Mode
T1
=
2 sec.
T1
=
4 sec.
T2
=
10 sec.
2-Wire
Momentary
Mode
T1
=
2 sec.
T2
=
10 sec.
QD Mode
(default)
T1
=
20 sec.
T2
=
4 sec.
T3
=
10 sec.
3-Wire
Mode
T1
=
5 sec.
T2
=
2 sec.
T3
=
10 sec.
Gen
Type
Relay Timing/Operation (RY1/RY2/RY3)
Time
Period
2-Wire
Maintain
Mode
Generator: Quiet Diesel Series (Onan). HDZAA model is not compatible
with the AGS-N module – damage may occur.
Generators: Marquis, Emerald, and Microquiet (Onan); Quiet Pack Series
(Generac).
Generator: EM Series with remote control (Honda).
Generators: RMY Series (Kohler); DynaGen controllers.
Generator: PT-ECU-63 controller with 2-wires (Powertech).
ON
4
3
2
1
ON
4
3
2
1
ON
4
3
2
1
T2
=
10 sec.
RY3
(N.O.)
RY3
(N.O.)
ON
4
3
2
1
RY1
(N.O.)
RY2
(N.O.)
T1
GEN RUN PD.
T3
T2
T3
RY3
(N.O.)
RY1
(N.O.)
RY2
(N.O.)
T2
T1
T1
GEN RUN PD.
RY1
(N.O.)
RY3
(N.O.)
RY2
(N.O.)
T3
=
5 sec.
T3
RY2
(N.O.)
RY3
(N.O.)
T1
T2
GEN RUN PD.
T1
=
4 sec.
T2
=
10 sec.
2-Wire
Standby
Mode*
Generators: Two-wire start (does not require gen run voltage signal to
Terminal #2).
ON
4
3
2
1
T1
=
10 sec.
T2
=
14 sec.
5-Wire
Mode
Generators: BTDA / BEG (Westerbeke), 205-DS (Martin Diesel), NL-673
(Northern Lights).
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
T3
=
4 sec.
T4
=
25 sec.
T1
T2
T3
T1
T4
T1
GEN RUN PD.
RY1
(N.O.)
ON
4
3
2
1
* ME-AGS-N Revision 5.2 or higher required
Table 3-1, Gen Type Settings