Magnetrol STI Echotel 919 Installation And Operating Manual Download Page 4

Echotel Model 919 Ultrasonic Level Switch

2

2.0

Installation

2.1

Unpacking

Unpack the instrument carefully. Inspect all units for 
damage. Report any concealed damage to carrier within
24 hours. Check the contents of the packing slip and
purchase order. Check and record the serial number for
future reference when ordering parts.

2.2

Electrostatic Discharge (ESD) Handling
Procedure

Magnetrol’s electronic instruments are manufactured to the
highest quality standards. These instruments use electronic
components that may be damaged by static electricity pres-
ent in most work environments. 

The following steps are recommended to reduce the risk
of component failure due to electrostatic discharge.

• Ship and store circuit boards in anti-static bags. If an anti-

static bag is not available, wrap the board in aluminum
foil. Do not place boards on foam packing materials.

• Use a grounding wrist strap when installing and removing 

circuit boards. A grounded workstation is recommended. 

• Handle circuit boards only by the edges. Do not touch

components or connector pins.

• Make sure that all electrical connections are completely

made and none are partial or floating. Ground all equip-
ment to a good, earth ground. 

2.3

Before You Begin

Each Model 919 is built to match the specific physical
specifications of the required installation. Make sure the
transducer process connection is correct for the threaded
or flanged mounting on the vessel or tank where the
switch will be located. 

See Mounting, Section 2.4

.

For the relay version of the Model 919, make sure that the
input power will be 24 VDC ±10%. The all voltage version
of the 919 must be used in series with a load. 

See Wiring,

Section 2.5

.

CAUTION

SENSITIVE ELECTRONIC DEVICES

DO NOT SHIP OR STORE NEAR STRONG

ELECTROSTATIC, ELECTROMAGNETIC,

MAGNETIC, OR RADIOACTIVE FIELDS

Summary of Contents for STI Echotel 919

Page 1: ...Installation and Operating Manual Ultrasonic Level Switch Echotel Model 919 Model 919 with sanitary fitting Model 919 with 3 4 NPT...

Page 2: ...ion is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired...

Page 3: ...m liquid level measurement in a wide variety of process media and application conditions The transducer uses a pair of piezoelectric crystals that are encapsulated in epoxy at the tip of the transduce...

Page 4: ...aluminum foil Do not place boards on foam packing materials Use a grounding wrist strap when installing and removing circuit boards A grounded workstation is recommended Handle circuit boards only by...

Page 5: ...ead tape If flanged bolt unit to mating flange with proper gasket The Valox housing can be rotated up to 330 degrees to align with the conduit Caution Never tighten unit on the tank connection by turn...

Page 6: ...PROCEDURES 1 Make sure the power is turned off 2 Remove the housing cover 3 Prevent moisture seepage into housing by installing an approved seal drain fitting in the conduit run leading to the unit 4...

Page 7: ...unit 4 Pull twisted shielded pair wire through the conduit connection 5 Connect the hot lead from the power supply to the middle 24 240 VAC VDC position of the terminal block 6 Connect the return lead...

Page 8: ...high level failsafe or WET ON for low level failsafe Figure 12 can be used for proper failsafe configuration NO CM NC Energized De energized Energized De energized HL High level failsafe LL Low level...

Page 9: ...housing 1 2 NPT 2 95 75 Echotel Model 919 Ultrasonic Level Switch 7 3 0 Reference Information 3 1 Troubleshooting 1 No signal with level change a Check wiring to make sure proper input voltage is supp...

Page 10: ...bar maximum Process Temperature Without heat extension 40 to 250 F 40 to 120 C With heat extension 40 to 300 F 40 to 150 C Housing Material Valox PBT Ingress Protection NEMA 4X IP67 Shock ANSI ISA S71...

Page 11: ...1 2 NPT conduit connection M Relay version with single PG 13 5 conduit connection R Relay version with single 1 2 NPT conduit connection 0 English actuation length in inches 1 Metric actuation length...

Page 12: ...e factory inspection finds the cause of the claim to be covered under the warranty If the trouble is the result of conditions beyond our con trol or is NOT covered by the warranty there will be charge...

Reviews: