background image

10

57-657 SIL Certified Safety Manual for ECLIPSE Model 706

Step

Action

4

Use the DIAGNOSTICS menu to perform a “CURRENT LOOP TEST”. Select DIAGNOSTICS /
ADVANCED DIAGNOSTICS / TRANSMITTER TESTS / Analog Output Test to change the output loop
current and confirm the actual current matches the value chosen. 

a.) Send a HART command to the transmitter (or use the local interface) to go to the high alarm

current output, 22 mA, and verify that the analog current reaches the valve.

i.) This step tests for compliance voltage problems such as low supply voltage or increased

wiring resistance. 

ii.) This also tests for current loop control circuitry and adjustment problems.

b.)  Send a HART command to the transmitter (or use the local interface) to go to the low alarm

current output, 3.6 mA, and verify that the analog current reaches the valve.
i.) This step tests for high quiescent current and supply voltage problems. 

ii.) This also tests for current loop control circuitry and adjustment problems.

c.) Exit the “Analog Output Test” and confirm that the output returns to its original state—with the

proper loop current as indicated and controlled by the unit.

Use the DIAGNOSTICS menu to observe the present Echo Curve. Confirm that the ECHO Waveform is
normal. The echo curve is dependent on the type of probe, the installation conditions and the level of
process on the probe. Comparison of the present Echo Curve to the one stored at the time of commis-
sioning the unit gives additional confidence of the normal operation of the unit. Use of the DTM and
digital communications is necessary for comparison of echo curves. 

a.) Select DIAGNOSTICS/ ECHO CURVE/ View Echo Curve

i.) Observe the present Echo Curve, identify the characteristic portions of the waveform related

to the FIDUCIAL, Process level, End of Probe and other features.

ii.) Confirm that the FIDUCIAL appears acceptable. Confirm the FIDUCIAL is located where

expected.

iii.) Confirm that the signal from the process level appears normal and is located as expected. 
iv.) Verify that the baseline of the waveform is smooth and flat.

v.) Compare to Echo Curve from commissioning in the FIDUCIAL area. 

b.) Access the Fiducial Ticks and Fiducial Strength values in the menu: DIAGNOSTICS /

ADVANCES DIAGNOSTICS / INTERNAL VALUES

i.) Observe and record:

1.) Fiducial Ticks _____________
2.) Fiducial Strength _____________

ii.) Confirm that these values match the previous values.

1.) Fiducial Ticks differs within ±100
2.) Fiducial Strength differs within ±15

6

Perform two-point calibration check of the transmitter by applying level to two points on the probe and
compare the transmitter display reading and the current level value to a known reference measurement. 

7

If the calibration is correct the proof test is complete. Proceed to step 9.

8

If the calibration is incorrect, remove the transmitter and probe from the process. Inspect the probe for
buildup or clogging. Clean the probe, if necessary. Perform a bench calibration check by shorting the
probe at two points. Measure the level from the bottom of the probe to the two points and compare to
the transmitter display and current level readings. 

a.) If the calibration is off by more than 2%, contact the factory for assistance. 

b.) If the calibration is correct, the proof test in complete.

c.) Re-install the probe and transmitter. 

9

Restore loop to full operation. 

10

Remove the bypass from the safety PLC to restore normal operation.

Summary of Contents for ECLIPSE 706 Series

Page 1: ...n the output will be driven to the customer specified out of range signal i e 3 6 mA or 21 mA The Enhanced Model 706 is certified for use in low demand level measurement applications Application The H...

Page 2: ...ronmental 6 6 1 2 1 Operating 6 6 1 2 2 Storage 6 6 2 Installation 6 6 3 Skill Level of Personnel 6 6 4 Necessary Tools 7 6 5 Configuration Information 7 6 5 1 General 7 6 5 2 Configuration 7 6 5 3 Wr...

Page 3: ...the liquid level The amplitude of the reflection depends on the dielectric con stant of the product The higher the dielectric constant the larger the reflection 1 3 Determining Safety Integrity Level...

Page 4: ...Serial Number shown on the name plates 3 0 Level Measuring System The diagram at left shows the structure of a typical measuring system incorporating the ECLIPSE Model 706 transmitter This SIL 2 3 Ce...

Page 5: ...an Time To Repair MTTR SIL determinations are based on a number of factors including the Mean Time To Repair MTTR The analysis for the ECLIPSE Model 706 is based on a MTTR of 24 hours 5 0 Supplementar...

Page 6: ...Manual 57 606 for Environmental limitations 6 1 2 1 Operating The operating temperature range is 40 to 175 F 40 to 80 C 6 1 2 2 Storage The device should be stored in its original shipping box and not...

Page 7: ...nfiguration Ensure the Model 706 transmitter has been properly config ured for the application and probe Special consideration should be given to the following configuration parameters Dielectric Rang...

Page 8: ...nse Times Continuous internal diagnostics are present within the Enhanced ECLIPSE Model 706 transmitter In the event a Fault is detected a message will appear on the LCD and the output current will be...

Page 9: ...indicate OK b Choose the menu DIAGNOSTICS EVENT HISTORY Event Log i Any FAULT or WARNING messages must be investigated and understood ii Corrective actions should be taken for FAULT messages continued...

Page 10: ...curves a Select DIAGNOSTICS ECHO CURVE View Echo Curve i Observe the present Echo Curve identify the characteristic portions of the waveform related to the FIDUCIAL Process level End of Probe and othe...

Page 11: ...figuration parameters avail able via the Local User Interface during normal operation The end user will enable the User Password to lock out any end user modifiable configuration parameters avail able...

Page 12: ...will respond to a change from the user s process within the safety function response time The Eclipse Model 706 shall transition to the Faulted Mode from the Normal Mode within the Diagnostic Test Int...

Page 13: ...13 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 0 Appendices 9 1 SIL Certificate...

Page 14: ...14 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 2 FMEDA Report exida Management Summary...

Page 15: ...itself and its operating conditions The assumption of a constant failure rate is based on the bathtub curve Therefore it is obvious that the PFDavg calculation is only valid for components that have...

Page 16: ...Mod Guideline on the Implementation of ANSI ISA 84 00 01 2004 Service Policy Owners of MAGNETROL controls may request the return of a control or any part of a control for complete rebuilding or replac...

Reviews: