background image

F

OUNDATION

Fieldbus

Operating Manual

Enhanced Model 2xx

F

OUNDATION

Fieldbus

Digital Output

Software v3.x

A Magnetrol Company

Magnetostrictive

Level Transmitter

Summary of Contents for 2xx

Page 1: ...FOUNDATION Fieldbus Operating Manual Enhanced Model 2xx FOUNDATION Fieldbus Digital Output Software v3 x A Magnetrol Company Magnetostrictive Level Transmitter...

Page 2: ...n Category II Pollution Degree 2 If equipment is used in a manner not specified by the man ufacturer protection provided by the equipment may be impaired Notice of Trademark Copyright and Limitations...

Page 3: ...14 3 4 User Calibration Parameters 14 3 4 1 Factory Parameters 14 3 4 2 Firmware Version 15 3 5 Analog Input Block 15 3 5 1 AI Block Parameters 15 4 0 Diagnostic Parameters 17 4 1 Simulation Feature 1...

Page 4: ...ble the varying 4 20 mA current a dig ital communications scheme such as FOUNDATION fieldbus considers the two wires as a network The network can carry many process variables as well as other informat...

Page 5: ...d control are the result A FOUNDATION fieldbus system allows for mul tiple variables to be brought back from each device to the control room for additional trending and reporting 3 Maintenance The sel...

Page 6: ...tor is placed between the power supply in the safe area and the device in the hazardous area H1 also supports the Fieldbus Intrinsically Safe Concept FISCO model which allows more field devices in a n...

Page 7: ...Check and record the serial number for future reference when ordering parts Caution Do not discard the shipping container until all parts are accounted for and inspected 2 2 Electrostatic Discharge E...

Page 8: ...ly and the Jupiter transmitter is correct for the type of installa tion See Specifications Section 5 3 NOTE Applying incorrect voltage will damage the unit When installing the Jupiter transmitter in a...

Page 9: ...rmation Some key information is needed to configure the Jupiter transmitter Complete the following operating parameters table before beginning configuration Display Question Answer Units What units of...

Page 10: ...essary use strapping tape to temporarily hold in place on the MLI See Figure 1 6 Position the upper clamp to attach the unit to the MLI and tighten See Figure 1 7 Discard any tape temporarily holding...

Page 11: ...power is applied to the instrument Equipment installed in an area classified as Class I Div 2 reflects that flammable or explosive vapors may be present To install intrinsically safe wiring make sure...

Page 12: ...arameters common to all blocks Additional information for a given parameter is described later in that specific block section ST_REV static data revision a read only parameter that gives the revision...

Page 13: ...2 Resource Block The RESOURCE block contains data specific to the Enhanced Jupiter transmitter along with some information about the firmware NOTE The Resource Block has no control function MODE_BLK M...

Page 14: ...interval between copies of non volatile NV parameters to NV memory NV mem ory is only updated if there has been a significant change in the dynamic value and the last value saved will be available for...

Page 15: ...the static data in the block BLOCK_ALM Block Alarm is used for configuration hardware connection or system problems in the block The cause of any specific alert is entered in the subcode field The fir...

Page 16: ..._EVT Update Event an alert generated by a write to the static data in the TRANSDUCER block Another important parameter found later in the TRANS DUCER block list is DEVICE_STATUS which displays the sta...

Page 17: ...de the ability to monitor changes and adjustments to a transmitter The Fieldbus concept allows a user to make calibration adjustments if deemed necessary NOTE The original factory calibration settings...

Page 18: ...ually supplied when simulate is enabled When simulate is disabled the simulate value and status track the actual value and status XD_SCALE The high and low scale values engineering units code and numb...

Page 19: ...The block alarm is used for all configuration hardware connection failure or system problems in the block ALARM_SUM The current alert status unacknowledged states unreported states and disabled state...

Page 20: ...ng OOS or the AI Block not scheduled for execution 5 L TYPE not set or set to Direct with improper OUT_SCALE The AI uses the STATUS_OPTS setting and the TRANS DUCER PV LIMIT value to modify the AI PV...

Page 21: ...level the transmitter maintains the last good value as the output and flags the failure The LIMIT attrib ute is the same as the last good measurement Excessive dis rupted cycles causes the transmitter...

Page 22: ...Probe bent Chamber Float inside the level gauge is moving slow Ensure that the magnetic level indicator is plumb or not at all The process fluid being measured may be too viscous and heat tracing may...

Page 23: ...p Present temperature in electronics Transmitter may need to be moved compartment is above 80 C to ensure temperature is within specification Float 2 No level signal detected from float 2 Make sure 2...

Page 24: ...e network one at each end of the segment Cable length plus spur length must not exceed the following values The cable shield is to be hard grounded only at one point close to the DCS In addition the c...

Page 25: ...TION M20 conduit connections not CSA approved explosion proof FM approval Class II Div 2 Groups F G only Materials marked as category 1 equipment and used in hazardous areas requiring this category sh...

Page 26: ...46 649 Jupiter Magnetostrictive Transmitter FOUNDATION fieldbus 23 5 2 3 Agency Drawing...

Page 27: ...24 46 649 Jupiter Magnetostrictive Transmitter FOUNDATION fieldbus 5 2 3 Agency Drawing...

Page 28: ...eldbus General Purpose Explosion Proof 9 to 32 VDC 17 mA maximum current draw FISCO FNICO 9 17 5 VDC 17 mA maximum current draw Housing Material Aluminum A356T6 0 20 copper optional 316 stainless stee...

Page 29: ...gh Temperature Bend Gemini Bottom Mount Offset and Secondary Transmitter MADE INUSA MADE INUSA MADE INUSA MADE INUSA MADE INUSA MADE INUSA 11 279 8 203 11 5 292 12 5 318 11 279 8 203 11 5 292 12 5 318...

Page 30: ...1 Replacement Parts Item Description Part Number Electronic module Display FOUNDATION fieldbus 031 2840 001 Terminal board FOUNDATION fieldbus 030 9151 004 O ring Viton 012 2201 237 Aluminum housing...

Page 31: ...Monel 200 F 95 C Maximum 5 Electropolished 316 316L SS 200 F 95 C Maximum 6 Sanitary 316 316L SS 200 F 95 C Maximum MATERIALS OF CONSTRUCTION 1 Cast Aluminum Integral Mount with 3 4 NPT Conduit Entry...

Page 32: ...lange 6K 4 600 RTJ ANSI Flange 6L 4 900 RTJ ANSI Flange 6M 4 1500 RTJ ANSI Flange 6N 4 2500 RTJ ANSI Flange 6P 4 3A Tri Clamp Material Code 6 only BA DN50 PN16 DIN 2527 Form B Flange BB DN25 PN25 40 D...

Page 33: ...2 75 float 50 70 mm NA 2 00 2 75 float 50 70 mm PA 1 85 3 00 float 47 76 mm QA 2 00 2 75 float 50 70 mm 1 00 1 12 MB 2 00 2 75 float 50 70 mm NB 2 30 3 00 float 58 5 76 mm PB 1 85 3 00 float 47 76 mm...

Page 34: ...Probe Length 30 DEADBAND Deadband 31 SENSOR_MOUNT Sensor Mount 32 TRIM_LEVEL Trim Level 33 INTERFACE Interface ITEM PARAMETER NAME PARAMETER LABEL 34 INTERFACE_UNIT Interface Unit 35 TRIM_INTERFACE T...

Page 35: ...ric Tag Serial TROUBLESHOOTING Level Correct Value Incorrect Value Units Probe Length Level Offset Deadband Sensor Mount Conversion Factor Scale Offset Float 1 Threshold Float 1 Polarity Float 2 Thres...

Page 36: ...from the fac tory prior to the material s return This is available through Magnetrol Orion s local representative or by contacting the factory Please supply the following infor mation 1 Company Name...