MicroDrive Access and Parking
Assembly and installation
5815,5013US / Version 05
55
Laying the foundation,
installing empty conduits
Fig. 16: Foundation plan for light barrier post
Dimensions in inch or feet are without parenthesis. Dimensions in
mm are in parenthesis.
1
Foundation anchor (4 pcs.)
2
Concrete foundations (C35/45 XD3 XF2)
3
Optional for light barriers:
Empty conduit for receiver connection line
4
Foundation depth: at least 800 mm, frost-protected
foundation depth to be adjusted to the local situation.
1. Dig foundation hole pursuant to Fig. 13 and Fig. 16.
2. Place empty conduit pursuant to Fig. 16 in the foundation
hole.
3. Close empty conduit to prevent water from entering.
4. Fill concrete foundation pursuant to Fig. 16.
5. Create flat line in the base area. The following requirements
must be fulfilled:
Level and horizontal.
Surface deviation: max. 0.00732 in/ft
2
(2 mm/m
2
)
6. Let concrete cure.
Summary of Contents for MHTM MicroDrive Access Series
Page 4: ...Barrier MHTM TM MicroDrive Access and Parking 4 5815 5013US Version 05...
Page 126: ...Barrier MHTM TM MicroDrive Access and Parking 126 5815 5013US Version 05...
Page 129: ......
Page 130: ...Barrier MHTM TM MicroDrive Access and Parking 130 5815 5013US Version 05...
Page 132: ...Barrier MHTM TM MicroDrive Access and Parking Appendix 132 5815 5013US Version 05...
Page 134: ......
Page 136: ......
Page 138: ......
Page 140: ......