1)
MOUNTING
Mount the iCoin to the faceplate of the meter box using the
holes on the stainless steel edgemount bracket. On the
CP990 the middle left mounting hole may or may not be
used as it does have restricted access due to the display
enclosure. Ensure that the iCoin is mounted vertically and
is not tilted in any direction.
2)
ELECTRICAL CONNECTION
Wire connections for the CP990 & CP890 are shown in the following chart. Before
connecting power to the iCoin, check the supply voltage with a voltmeter.
When turning power o
ff
and on to the iCoin power must remain o
ff
for a minimum of
10 seconds before being turned back on to ensure that the iCoin powers up
correctly.
Model
Power
Requirements
Power Connections
Pulse Connections
CP990
CP890
24±5 VAC
Black –
Blue (
Note 1
)
Purple (
Note 2
)
CP990-R
CP890-R
Red w/green stripe (
Note 3
)
Red w/green stripe (
Note 3
)
CP990-D
CP890-D
12 to 30 VDC
Red +
Black –
Blue (
Note 1
)
Purple (
Note 2
)
CP990-DR
CP890-DR
Red w/green stripe (
Note 3
)
Red w/green stripe (
Note 3
)
Note 1:
The blue wire is a DC switch used for pulsing that will sink a maximum of
200mA at 5-36 VDC to black –.
Note 2:
The purple wire is an AC switch used for pulsing that will sink a
maximum of 500mA up to 24 VAC to black –.
Note 3:
The two red wires with green stripe (non-polarized) are a normally open
contact used for pulsing rated at a maximum resistive load (non inductive) 1A,
125 VAC, 60 VDC.
Optional
Mounting
Hole