background image

Page 6 of 15

506325-01

Issue 1734

Figure 4. Securing Unit

Installation

Brackets

Remove and replace screw to secure bracket

(one each side)

Do not screw into the side of the drain pan, or into the 

indoor coil or heat strip.

 CAUTION

Air Filter

All indoor return air must be filtered. A washable filter is 

furnished with the unit, located in the return air opening. 

If return duct is installed, provisions must be made to 

accommodate  filter  servicing.  If  a  filter  is  installed  at  a 

separate central return location, then the factory furnished 

filter must be removed from the unit.

The  filter  should  be  cleaned  at  least  three  times  during 

each of the heating and cooling seasons, or more 

frequently if unusual conditions are encountered. To clean 

the washable filter, shake filter to remove excess dirt and/

or use a vacuum cleaner. Wash filter in soap or detergent 

water and replace after filter is dry. It is not necessary to oil 

the filter after washing.

If an installation is made in which it is more desirable to 

mount the filter exterior to the unit, in the return duct work 

or elsewhere, the washable filter can be used or replaced 

with a disposable filter. If a disposable filter is used, use the 

information provided in Table 3 when sizing the disposable 

filter.

Table 3. Minimum Required Surface Area for 

Disposable Filters

Model Number

Filter Area

MHP*12

192 square inches

MHP*18

288 square inches

MHP*24

384 square inches

MHP*30-36

480 square inches

* 9 and 10 EER Models

Condensate Drain

Provisions must be made to properly drain the indoor and 

outdoor drain pans of this appliance.

Indoor  drain  connection:  1/2”  NPT  to  3/4”  PVC  fitting 

(schedule 40). Outdoor drain connection: 3/4” NPT to 3/4” 

PVC fitting (schedule 40 minimum). Both drains must be 

trapped as shown in Figure 5. The drain line should pitch 

gradually downward at least 1” per 10’ of horizontal run to 

open drain.

If local codes require the use of metal condensate lines, do 

not thread metal fittings into the unit drain pan. A 1/2” x 3/4” 

threaded plastic nipple is available from the manufacturer 

as a kit (see the 

Accessories

 section). Thread the 1/2” 

end of the nipple into the unit drain pan and make the field 

connection to the 3/4” end. 

Use  thread  sealant  on  the  threaded  fittings.  Install 

threaded fittings by hand only. 

Do not over torque the 

fittings.

Do  not  thread  metal  condensate  fittings  to  unit  drain 

pan.

 CAUTION

Figure 5. Condensate Drain Installation

Fresh Air Intake (Fresh Air Models Only)

On fresh air capable models (designated by the FA in the 

model number – e.g. 7MHP4-10-301FP), up to 5% fresh 

air is drawn into the unit from outside when the indoor 

blower comes on.

To access the fresh air intake feature, the threaded cap 

must be removed from the fresh air intake pipe (see Figure 

6). The fresh air intake pipe is located at the rear of the unit 

return air intake. When not in use, cap should be placed 

nearby in the air intake area in case it is needed in the 

future.

Summary of Contents for MHP4-09-12

Page 1: ...est edition in the United States the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should...

Page 2: ...carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Table 1 Application Limitations Outdoor Ambient Air Temperature F Minimum D...

Page 3: ...the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit If a return duct is not installed in order to provi...

Page 4: ...nd the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional suppo...

Page 5: ...ecommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems...

Page 6: ...inches MHP 18 288 square inches MHP 24 384 square inches MHP 30 36 480 square inches 9 and 10 EER Models Condensate Drain Provisions must be made to properly drain the indoor and outdoor drain pans o...

Page 7: ...e contactor Cooling When the thermostat is in the cooling mode the O circuit is powered which energizes the reversing valve Upon cooling demand the thermostat closes circuit R to Y and G Closing R to...

Page 8: ...oting of the defrost system see Figure 8 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures are such that the switch wi...

Page 9: ...air circuit Cleaning should be as often as necessary to keep the coil clean To clean the coil remove the lower access panel and blow out debris by using compressed air or water Be sure power to unit i...

Page 10: ...ASLEEVE 3 Wall Sleeve Kit 45 Louver MHP4 09 12 18 ASLEEVE2 1 2 Wall Sleeve Kit MHP4 09 12 18 24 30MHP4 10 18 24 ASLEEVE2 2 2 Wall Sleeve Kit MHP4 10 30 MHP4 09 36 ASLEEVE6 1 6 Wall Sleeve Kit MHP4 09...

Page 11: ...10 3 10 45 45 1 8 ASLEEVE10 4 10 45 45 1 8 ASLEEVE12 1 12 29 29 1 8 ASLEEVE12 2 12 32 3 4 32 7 8 ASLEEVE12 3 12 45 45 1 8 ASLEEVE12 4 12 45 45 1 8 ASLEEVE 3 45 45 1 8 Thru the wall installations only...

Page 12: ...ITOR RUN CONDENSER FAN COMP CONNECTOR BLOCK BLUE GREY COOLING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH ML FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLAC...

Page 13: ...SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF DEFROST RELAY FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST SENSOR DEFROST CONTROL BLOWER CONTROL COM 20...

Page 14: ...LING R G Y O BLACK BLACK X FRmR X FRmC GRAY BROWN C H MH L FUSE BLUE BLUE COM RVG RV O Y W R DFS2 DFS1 C C DF1 LIGHT BLUE REVERSING VALVE BLACK BLACK O O ORANGE WHITE RED BLACK BLACK DEFROST CONTROL B...

Page 15: ...IT SEQ C RVG CC O Y W R DFS DFS C TRANSFORMER REVERSING VALVE COIL DF DF FAN MOTOR DUAL CAPACITOR CONTACTOR L1 T1 C R S 208 230V 1 60HZ DEFROST CONTROL BLOWER CONTROL COM 208 240 24 V G CONTACTOR COIL...

Reviews: