background image

Page 18 of 20

507389-02

Issue 1733

Combustion 

Inducer

Snap into 

place 

first

 

(visible after 

reinstalled 

in unit)

Inducer 

Orifice

Then snap 

into place

Figure 12. 

1. 

The combustion orifice is held in place with snap-fits at 

the inducer inlet and at the indicator tab at the inducer 

mounting foot.

2.  With the combustion inducer out of the unit, carefully 

pry  the  round  portion  of  the  orifice  from  the  inducer 

inlet.

3.  Remove the indicator tab from the inducer mounting 

foot.

4.  For reassembly, follow the above steps in reverse 

order.

Furnace Condensate Drain

The condensate drain ensures proper evacuation of 

furnace  condensate  from  the  collector  box  and  flue  out 

of the cabinet. If hoses are disconnected or if the drain 

is removed and replaced, the drain must be primed as 

described in the procedure outlined in the “Start-up” 

section. To remove the condensate drain:

1.  Disconnect the upper and lower drain hoses at the 

condensate drain.

2.  Remove the two screws that secure the drain to the 

vest panel.

3.  For reassembly, follow the above steps in reverse 

order.

4.  Prime the condensate drain as described in the 

procedure outlined in the “Start-up” section.

Condensate Heater Thermostat

1.  Disconnect the two lead wires at the thermostat.

2.  Remove the three screws that secure it to the panel 

and pull the thermostat free.

3.  For reassembly, follow the above steps in reverse 

order.

Condensate Heater

1. 

Remove  the  control  board  mounting  bracket  as 

described previously.

2.  Remove the furnace condensate drain, and upper and 

lower hoses as described previously.

3.  Disconnect the two lead wires at the “24VAC” and 

“GND” terminals on the ignition control board.

4. 

Remove  the  drain  fitting  by  disconnecting  the  drain 

line and:
a. 

When side-exit drain is used, slide the fitting to the 

left to disengage it from the division panel, then 

lift out.

b. 

When front-exit drain is used, slide the fitting away 

from you to disengage it from the division panel, 

then lift out.

5.  Remove the screw securing the heater panel to the 

vest panel.

6.  Remove the 2 side panel screws on either side of the 

drain fitting and “flex” the panel outward as you pull 

the heater panel toward you, out of the compartment. 

7.  For reassembly, follow the above steps in reverse 

order.

Heat Exchanger Inspection

The heat exchanger should be inspected periodically and 

cleaned if necessary. The assembly can be inspected 

in place, but cleaning requires accessing both ends 

of the primary and secondary tubes, which can only be 

accomplished by removing the heat exchanger assembly 

from the furnace cabinet. To access the primary heat 

exchanger tubes for inspection:

1.  Remove the burner & manifold assembly as described 

previously.

2. 

Remove  the  control  board  mounting  bracket  as 

described previously.

3. 

Check  the  tubes  for  evidence  of  soot.  If  the  tubes 

are clean, reassembly is the reverse of the above 

procedure. If there is noticeable soot, continue with 

the heat exchanger removal procedure to remove and 

clean the heat exchanger.

Summary of Contents for HWC9 V-Series

Page 1: ...in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Do not store combustible materials near the furnace or warm air ducts The m...

Page 2: ...r portions of the unit may be surrounded by a closet with minimum clearances to combustible material of 0 sides 2 top and 1 front and plenum Adequate clearance must be provided to install gas line uni...

Page 3: ...tion air requirements during construction The furnace heat exchanger components duct system air filters and evaporator coils must be thoroughly cleaned following final construction clean up All furnac...

Page 4: ...led in an unconditioned space the condensate drain elbow outside the unit cabinet must have heat tape suitable for PVC pipe installed and the elbow insulated This heat tape and insulation are field su...

Page 5: ...ate Drain Component Locations Side Exit Figure 4 Furnace Condensate Drain Component Locations Front Exit Condensate Trap Side Panel Upper Drain Hose from Collector Box Lower Drain Hose to drain fittin...

Page 6: ...art of the appliance The venting system must not be modified or added on to The unit contains a combustion inducer The inducer draws the combustion products out of the heat exchanger and forces them f...

Page 7: ...must be used Do not use a connector which has previously serviced another gas appliance A manual shutoff valve must be located outside the unit The use of a union located upstream of the controls is...

Page 8: ...ional Electrical Code ANSI NFPA No 70 latest edition for installations in the U S or the Canadian Electrical Code Part 1 CSA C22 1 latest edition for installations in Canada See rating plate for minim...

Page 9: ...6 deep Insert the duct into the return opening in the bottom of the unit and flange the duct over the existing flanges around the opening inside the unit Make sure that all sides of the duct are flang...

Page 10: ...615 47 590 49 565 51 TAP 2 HEAT 208 or 230 780 37 755 38 730 39 710 40 TAP 3 HEAT 208 or 230 900 32 875 33 855 34 835 34 TAP 4 COOL 208 or 230 605 575 545 520 TAP 5 COOL 208 or 230 650 615 585 555 HWC...

Page 11: ...615 N A 590 N A 565 N A TAP 2 HEAT 208 or 230 780 61 755 63 730 65 710 67 TAP 3 HEAT 208 or 230 900 53 875 54 855 55 835 57 TAP 4 COOL 208 or 230 800 775 755 735 TAP 5 COOL 208 or 230 880 860 835 815...

Page 12: ...ode A high altitude conversion kit available from the manufacturer and approved for this purpose must be used Installation and Operation in Extremely Cold Weather Areas In areas where extremely cold b...

Page 13: ...satisfied the burners and combustion blower shut off 7 Circulating air blower will shut off 120 seconds later If the burners should fail to ignite the ignition control will try to ignite the burners...

Page 14: ...ly Igniter Combustion Inducer Gas Valve Gas Manifold Rollout Switch Burner Manifold Assembly Primary Limit Heat Exchanger Access Panel Cold End Header Box Upper Drain Hose Inducer Elbow Flue Tube Drai...

Page 15: ...Page 15 of 20 507389 02 Issue 1733 Figure 11 Burner Manifold Assembly Removal Step 7 Mounting Brackets Step 8 Burner Manifold Assembly Step 9 Step 10...

Page 16: ...m the vest panel 10 Finally pull the assembly from the unit 11 Once the burner assembly is removed the burners can be cleaned using a bottle brush 12 For reassembly follow the above steps in reverse o...

Page 17: ...urner assembly 3 Remove the orifices by unscrewing them Do not use any pipe thread sealant during reassembly 4 For reassembly follow the above steps in reverse order Combustion Inducer The combustion...

Page 18: ...Heater 1 Remove the control board mounting bracket as described previously 2 Remove the furnace condensate drain and upper and lower hoses as described previously 3 Disconnect the two lead wires at th...

Page 19: ...ing chassis normally requires no maintenance since it is a closed self contained system System is charged with R410A refrigerant Periodic maintenance is limited to Cleaning the air filter Follow direc...

Page 20: ...GERANT HIGH PRESSURE SWITCH BLUE BLK WHT RED BLACK BLACK BLUE YELLOW OPERATING MODE CIRCUIT HEATING R W COOLING R G Y FAN R G ORG GREEN WHITE WHITE GREEN N G L C BLACK BLUE GREEN BLK WHT COOL HEAT UNU...

Reviews: