MADDALENA microCLIMA U Installation And Operating Instructions Manual Download Page 4

 

2015_03_03  

 

 

 

 

9) Tariff register 1: values 
alternating with tariff register 
number and criteria

2

 

 

 

 

10) Tariff register 2: values 
alternating with tariff register 
number and criteria

2

 

 

 

11) Momentary reading of 
the pulse counter 1 
alternating with the pulse 
value

2

 

 

 

12) Momentary reading of 
the pulse counter 2 
alternating with the pulse 
value

2

 

Level 2/Technician’s loop 

 

1) Maximum power in kW

 

 

2) Maximum flow in m³/h

 

 

3) Forward flow temperature 
in °C

 

 

4)  Return  flow  temperature 
in °C

 

 

5) Temperature difference

 

 

6) Days in operation since 
calibration

 

 

7) Sensor type/installation 
point

 

 

8) M-Bus address

 

 

9) Serial number

 

 

10) Firmware version

 

 

 

Level 3/Statistics loop 

 

 

1)  Previous  reading  date  alternating  with  its  value. 
Alternatively,  the  total  volume  or  tariff  values  can  be 
displayed

1

.

 

 

 

2 -16) Monthly values: dates alternating with their values.  

Alternatively,  the  total  volume  or  tariff  values  can  be 
displayed

1

.

 

Up to the

 

end of the month the consumption and reading date for that month will be shown as 0. 

2

It  can  be  set  using  the  software  “Device  Monitor”.  A  dedicated  meter  password  is  necessary.  The  password  is 

available from the manufacturer. 

8

 

Technical Data 

Approval Data

 

 

Nominal flow qp 

m³/h 

0.6 

1.5 

2.5 

3.5 

3.5 

6.0 

6.0 

Accuracy class 

 

EN 1434-1:2007; class 2/3 

Dynamic range; 
Minimum flow qi/qp 

 

1:50 

1:50 

1:100 
1:125 

1:100 

1:100 
1:125 
1:150 

1:100 
1:125 
1:150 

1:100 

1:100 

Maximum flow qs/qp 

 

2:1 

Mechanical class 

 

M1 

Electromagnetic class 

 

E1 

Protection class of flow sensor 

 

IP65 

Flow disturbance class 

 

U0 

Flow Sensor 

 

 

Nominal diameter DN 

mm 

15 

15 

20 

20 

25 

25 

25 

Summary of Contents for microCLIMA U

Page 1: ...guarantee and the approved application of the instrument are no longer valid To achieve measurement stability of the meter is it necessary that the water quality meet the requirements of the AGFW reco...

Page 2: ...up off the flow sensor For heat meter versions it is recommended to detach the calculator For heat cooling meters the calculator must be detached from the flow sensor 5 Mounting the Temperature Senso...

Page 3: ...alues that can be shown are divided into three display loops All data is retrieved using the push button next to the display At the start you are automatically in the main loop 1st level By pressing t...

Page 4: ...alternating with its value Alternatively the total volume or tariff values can be displayed 1 2 16 Monthly values dates alternating with their values Alternatively the total volume or tariff values ca...

Page 5: ...ata storage E2 PROM daily Display 8 digits special characters Interfaces standard infrared optional M Bus galvanically isolated M Bus galvanically isolated 2 pulse inputs wireless M Bus wireless M Bus...

Page 6: ...tallations of buildings Part 5 51 Selection and erection of electrical equipment Common rules IEC 60364 5 54 2011 03 Low voltage electrical installations Part 5 54 Selection and erection of electrical...

Page 7: ...ection 9 4 3 Activation of the radio interface 9 4 1 Technical data radio Frequency 868 MHz Transmission power up to 12 dBm Protocol wireless M Bus based on EN 13757 3 Selectable modes S1 T1 C1 Telegr...

Page 8: ...us or radio General information about pulse inputs It is important to note that the acknowledged state of the art technology rules and the relevant legal restraints international and local see 9 5 1 R...

Page 9: ...pulse without unit Installation notes for pulse inputs It is important that the pulse cables not be affected by or exposed to the M Bus voltage Check the polarity of pulse generators with open collect...

Page 10: ...tely in binary and hexadecimal form Binary display Description Hexadecimal display 1 at first place Low battery H 80 1 at second place Check sum error H 40 1 at third place E2 PROM defective H 20 1 at...

Page 11: ...being stored A defect on the calculator circuit board Rf sensor fault No calculations are carried out The registers for flow and energy are not being updated no new data is being stored Sensor cable...

Page 12: ...69168 Wiesloch Baiertal Germany Tel 49 0 6222 9800 0 Fax 49 0 6222 9800 50 E Mail info engelmann de www engelmann de 14 Contact Maddalena S p A Via G B Maddalena 2 4 33040 Povoletto UD Italy Tel 39 0...