Doc. code 1080100090 

 

 

Version: 2015_03_03 

 

 

 

 

 

2  

-

 

Further information can be obtained at www.engelmann.de. 

-

 

Instruments  which  have  been  replaced  or  exchanged  must  be  disposed  of  according  to  relevant 
environmental regulations. 

-

 

The display is deactivated and can be activated for one minute by pushing the button (except calculator 
without additional interfaces). 

3.1

 

Definition of pictograms on type identification label 

 

Installation in return flow 

 

Installation in forward flow 

4

 

Mounting the Flow Sensor 

4.1

 

Installation of 

S

ENSO

S

TAR

®

2/2+

 

type MSH-SStar in a single pipe connection piece (EAS) 

The multi-jet flow sensor type MSH-SStar has a 2“ connection as described in EN 14154 (IST) and must be installed 
without  an  adapter  in  a  single  pipe  connection  piece  (EAS)  compatible  to  EN  14154  (IST).  These  EASs  are  pipe 
connections which have no metrological influence on the measurement accuracy. 

Important 
Before installing the flow meter check if the EAS has the identification EN14154 (IST). If not, the label provided 
with the meter must be applied clearly to the EAS. 

Mounting 

-

 

Flush the pipes according to the generally acknowledged rules of technology. Then close all the shut-off 
valves. Open the nearest draining valve for pressure release. 

-

 

Drain the closed-off pipe section. 

-

 

Take into account the direction of flow (connection piece)! 

-

 

Remove the overflow flange or the old heat meter from the connection piece using a wrench. 

-

 

Remove all old gaskets. Check sealing surfaces and threads for imperfections or dirt. If necessary, deburr 
or clean with a suitable cleaning liquid. 

-

 

Place  the  new  profile  gasket  into  the  connection  piece  with  the  flat  surface  facing 
up.  

-

 

Lubricate the external thread of the flow sensor with a thin layer of food safe silicon 
grease. 

-

 

Check that the O-ring on the outlet of the flow sensor is in the correct position. 

-

 

Screw in the heat meter tightly by hand and then tighten additionally with a suitable 
wrench to the mechanical end stop (metal-to-metal). 

-

 

Detach the calculator and mount it, or rotate it to the best position for read-out.  

4.2

 

Installation of 

S

ENSO

S

TAR

®

2+

 

type MSH-VStar in a single pipe connection piece (ASS) 

The  multi-jet  flow  sensor  type  MSH-VStar  has  an  external  thread  M62x2  connection  as  described  in  EN  14154 
(TE1) and must be installed without an adapter in a single pipe connection piece (ASS) compatible to EN 14154 
(TE1). These ASSs are pipe connections which have no metrological influence on the measurement accuracy. 

Important 
Before installing the flow meter check if the ASS has the identification EN14154 (TE1). If not, the label provided 
with the meter must be applied clearly to the ASS. 

Mounting 

-

 

Flush the pipes according to the generally acknowledged rules of technology. Then close all the shut-off 
valves.  

-

 

Open the nearest draining valve for pressure release. 

-

 

Drain the closed-off pipe section. 

-

 

Take into account the direction of flow (connection piece)! 

-

 

Remove the overflow flange or the old heat meter from the connection piece using a wrench. 

-

 

Remove all old gaskets. Check sealing surfaces and threads for imperfections or dirt. If necessary, deburr 
or clean with a suitable cleaning liquid. 

-

 

Lubricate the external thread of the flow sensor with a thin layer of food safe silicon grease. 

-

 

Check that the O-ring on the outlet of the flow sensor is in the correct position. 

Summary of Contents for microCLIMA/SENSOSTAR 2 MSH

Page 1: ...must be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identification plate of the instrument and the...

Page 2: ...liquid Place the new profile gasket into the connection piece with the flat surface facing up Lubricate the external thread of the flow sensor with a thin layer of food safe silicon grease Check that...

Page 3: ...then tighten additionally with a suitable wrench to the mechanical end stop metal to metal Detach the calculator and mount it or rotate it to the best position for read out 4 4 Installation of SENSOST...

Page 4: ...ter s calculator can be detached from the flow sensor To release the calculator pull it carefully up off the flow sensor For heat meter versions it is recommended to detach the calculator For heat coo...

Page 5: ...ball valves and check installation points for leakage Protect the installation points meter and temperature sensors against manipulation by securing with the seals and sealing wires 6 Start of Operat...

Page 6: ...ernating display total cooling energy for heating cooling meter 2 Segment test all segments triggered simultaneously 3 Heat energy at last reading date alternating with last reading date1 4 Total flow...

Page 7: ...2007 class 2 3 Minimum flow qi qp horizontal standard 1 50 vertical Maximum flow qs qp 2 1 Mechanical class M1 Electromagnetic class E1 Protection class of flow sensor IP54 Flow disturbance class UO...

Page 8: ...he art technology rules and the relevant legal restraints international and local see 9 3 1 Relevant norms standards and literature are to be observed The installation has to be performed by authorize...

Page 9: ...the unused credit is stored in the instrument and can be used later During M Bus communication with an end instrument the other interfaces push button optical interface of this instrument cannot be us...

Page 10: ...settings may vary from the above 9 4 3 Activation of the radio interface The radio interface leaves the factory not activated It can be activated as follows a Without using additional software the rad...

Page 11: ...ns Part 5 54 Selection and erection of electrical equipment Earthing arrangements and protective conductors EN 50310 2010 Application of equipotential bonding and earthing in buildings with informatio...

Page 12: ...al free pulse output is an electronic switch that outputs counting pulses of the meter which can be used for any purpose The pulse output closes corresponding to the pulse value shown on the type iden...

Page 13: ...nating total heat and cooling energy with the exception of the hint reset 10 the instrument must be exchanged and sent to the supplier for examination 10 1 Hint description error description Hint Erro...

Page 14: ...MID Declaration of Conformity For the product described in this document we confirm as the manufacturer that it meets the fundamental requirements of the following directives Directive 2004 22 EC of 3...

Reviews: