Macurco RD-xx User Manual
REV – 2.1
[34-2900-0511-7 ]
6
|
P a g e
2.3
Features
•
ETL Listed to UL 61010-1 and CSA C22.2 No 61010-1
•
Low level meter with non-adjustable alarm set to 1,000 ppm refrigerant gas
•
Fan and alarm relay activation set at 1000 ppm
•
5 A SPDT fan relay controls starters of exhaust fans
•
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
•
4-20 mA Current Loop
•
RD-xx mounts on a standard 4x4 electrical box and becomes cover for the box
•
Supervised system: any internal detector problem will cause the fan & alarm relay to activate
•
Calibration kit is available.
2.4
Specifications
•
Shipping Weight: 1 pound (0.45 kg)
•
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 x 10.2 x 5.4 cm)
•
Color: White or Dark grey
•
Connections: plugs/terminals
•
Mounting box: (not included) 4x4 electric
•
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
•
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
•
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
•
Fan relay latching or not latching (default) selectable
•
Alarm relay: 0.5A 120 V, 60 VA
•
Alarm relay actuation: selectable N.O. (default) or N.C.
•
Current Loop: 4-20 mA for 0 or 1,000 ppm refrigerant gas, selectable to ’bAS’ (default), ‘EnH’, OFF
•
Buzzer: 85 dBA at 10cm settable to on (default) or off
•
Digital display: 3-digit LED
•
Operating environment 0°F to 125°F (-18°C to 52°C).10 to 90% RH non-condensing
2.4.1
6-Series Low Voltage
•
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
•
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
2.4.2
12-Series Line Voltage
•
Power: 100-240VAC (50 TO 60 HZ)
•
Current 1.0 A MAX