If a group has an equal number of sensors with gas readings greater than or equal the rising trip point and sensors with
readings less than or equal to the falling trip point, activating the output(s) is given priority.
It is up to the installer to ensure that the Quorum entry is appropriate for the configuration. Valid entries are from one to twelve, but a
value greater than the number of sensors being monitored by the group stops the group from controlling the outputs. The default Quorum
value is 1; in this case, only 1 sensor vote is needed to control the output.
8.5
Configure Signals Submenu
8.5.1
4.3.8 Configure Signals Submenu
Press Menu to display Hardware Summary
↑
x5 Configure Signals
→
Alarm Signals
A l a r m S i g n a l s
B u z z , H o r n , S t r o b e
Figure A-27 Alarm Signals
↑
Alarm Signal Buzzer (default 2 – Intermittent)
↑
Alarm Signal Horn (default 2 – Intermittent)
↑
Alarm Signal Strobe (default 1 – Continuous)
A l a r m S i g n a l s
B u z z : 2 I n t e r m i t .
Figure A-28 Buzzer Alarm Signal
→
Warning Signals
W a r n i n g S i g n a l s
H o r n : 5 O F F
Figure A-29 Horn Warning Signal
↑
Warn Signal Buzzer (default 5 – Off)
↑
Warn Signal Horn (default 5 – Off)
↑
Warn Signal Strobe (default 5 – Off)
→
Trouble Signals
T r o u b l e S i g n a l s
B u z z : 4 T r i p l e
Figure A-30 Buzzer Trouble Signal
↑
Trouble Signal Buzzer (default 4 – Triple Tap)
↑
Trouble Signal Horn (default 5 – Off)
↑
Trouble Signal Strobe (default 5 – Off)