54
E n t e r P a s s w o r d
_ _ _ _
Figure A-9 Enter Password
If the password is not entered correctly the panel will display as follows:
W r o n g P a s s w o r d
Figure A-11 Wrong Password Prompt
Once the current password has been entered, the panel will prompt for the configuration parameter being changed.
If the password has been lost:
→
Power down the DVP-120
→
Remove the Jumper Shorting Connector from the EXT header and place the Jumper Shorting Connector onto the top two pins of
the SYS header.
→
Power up the DVP-120. The first display is the current password on the unit.
→
Remove the Jumper Shorting Connector from the SYS header and install back onto the two bottom pins of the EXT header.
8.2
Configure Sensors Submenu
8.2.1
8.2.2
8.2.3
4.3 Setting the System Configuration
8.2.4
4.3.3 Configure Sensors Submenu
Press Menu to display Hardware Summary
↑
x 2 Configure Sensors
•
Sensor
S e n s o R 0 1 C O
A : 2 0 0 W : 5 0
Figure A-12 Sensor Summary
↑
Sensor type (set sensor type)
1=CO, 2=NO
2
, 3=EX, 4=NH
3
, 5=H
2
S, 6=REF, 7=CO
2
, 8=O
2
and 0=None
S e n s o r 0 1 C O
T y p e : 1
Figure A-13 Sensor Type