Macurco CD-xx H/MC Manual
REV
–
1.1
[34-2900-0510-8]
23
|
P a g e
t200
Sensor Expired
t400
Trouble Pressure Sensor
t800
Board not tested
*CD-xxH Only
**CD-xxMC Only
If the error mode repeats frequently, check for continuous power and proper voltage. If power is not the problem
and a unit has repeating error conditions, it may need to be returned to Macurco for service, per these User
Instructions.
42T
Note
42T
: If multiple error codes are occurring simultaneously, the different error codes will be added together into one
combined error code. Example: t08 and T80 occurring simultaneously will display as t88.
If the error mode indicates “Sensor expired” see section
5.2
Sensor Poisons
Unlike traditional catalytic bead and electrochemical sensors, IR sensors use a light source and a receptor to detect a specific
gas. Therefore, the sensor less likely to be affected by inhibitors or poison significantly enhancing safety and sensor life.
5.3
End-of-Life Signal
The CD-xxH/MC has a long life, the non-replaceable infrared sensor (IR Sensor). Fifteen (15) years after the CD-xxH/MC is
installed the sensor end-of-life signal will be activated indicating that the CD-xxH/MC has reached the end of its typical usable
life. The end-of-
life signal will cause an error code t200 “Sensor expired”. See section
signal can be silenced for 48 hours by pressing the "ENTER/TEST" button or by temporarily dropping power to the unit. The end-
of-life signal provides the user an opportunity to test and/or calibrate the sensor (CD-xxMC only) assuring that it is still
performing within acceptable parameters though the sensor is nearing the end of its expected life. The silence function will
continue to be available for 29 days after the CD-xxH/MC initiates the initial end-of-life signal. After this 29-day period, the CD-
xxH/MC can no longer be silenced, and the unit must be replaced.
WARNING
Do not disassemble unit or attempt to repair or modify any component of this instrument. This
instrument contains no user serviceable parts, and substitution of components may impair
product performance.
6
Maintenance
The CD-xxH/MC is low maintenance. The unit uses a long life NDIR sensor that has a 15-year life expectancy (in normal
conditions). The CD-6H uses an automated background calibration program to set the clean air level on a regular basis. The CD-
6H will maintain accuracy
if it is exposed to the “clean air reference value” (this reference value is the lowest concentration to
which the sensor is exposed) at least once per week.
The CD-6MC does not perform an automated background calibration and will need to be bump tested and calibrated to verify
functionality and accuracy of the sensor.
42T
Note:
42T
This applies when used in the typical indoor ambient air with weekly unoccupied periods.
All maintenance and repair of products manufactured by Macurco are to be performed at the appropriate Macurco
manufacturing facility. Macurco does not sanction any third-party repair facilities.
42T
Note:
42T
There is not a field calibration procedure for the Macurco CD-6H.
Summary of Contents for CD Series
Page 32: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 32 P a g e 9 2 Auto Test Menu bUZ ...
Page 33: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 33 P a g e 9 3 Configuration Menu CON ...
Page 34: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 34 P a g e ...
Page 35: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 35 P a g e ...
Page 36: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 36 P a g e ...
Page 37: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 37 P a g e ...
Page 38: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 38 P a g e ...
Page 39: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 39 P a g e 9 4 Select Test Menu tst ...
Page 40: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 40 P a g e 9 5 CAL Menu CD xxMC Only ...