© 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 37
Rev. Date 040218
3/8" Washer (4)
3/8"-16 Nylon Lock Nut (4)
3/8"-16 x 2 3/4" Hex
Head Bolts (4)
3/8" Washer (8)
Extension Bolt Kit
Safety Cable
Power
Sheilded Stranded CAT5e Cable
Safety Cable
Power
Shielded Stranded CAT5e Cable
Pull excess cable
through mount
2.2 All Rapid Mounts Industrial
Extension Tube
Safety Cable
Sheilded Stranded CAT5e Cable
Power Cable
Safety Cable
Shielded Stranded CAT5e Cable
Power Cable
Before Continuing:
1. Run the power cable to the mounting location.
2. Run the shielded CAT5e cable from the controller to the mount.
3. The communications cable
MUST
be routed at least 1 foot away
from power cables, high voltage power wires, and fluorescent lighting.
The only point where the power cable should be near the comm wire is
when they are in the mount and extension tube.
CAT5e Shielded must be used at a minimum. No unshielded comm cables.
NOTE
: Power cable must be routed into the mount on the
opposite side from safety cable and CAT5e cable.
NOTE
: For networks, please refer to the network controller or
AirLynk manual for CAT5e wiring instructions.