Seivice diagnosis
Domestic air conditioner
The temperatures detected by the thermistors are used to determine thermistor errors
when the thermistor input is more than 4.92V or less than 0.08V during compressor
operation.
Note: The values vary slightly in some models
Faulty connector connection
Faulty thermistor
Faulty PCB
* Caution
Be sure to turn off power switch before connect or disconnect connector,
or else
parts damage may be occurred.
Thermistor resistance check method:
Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester. The
relationship between normal temperature and resistance is shown in the value of indoor thermistor.
Method of
malfunction tection
Malfunction
detection conditions
*Thermistor
resistance check
Yes
Troubleshooting
E1: Room temperature sensor failure
E2: Heat-exchange sensor failure
LED1
flash 10 times
Defrost temperature sensor failure
LED1
flash 11 times
Suction temperature sensor failure
LED1
flash 12 times
Ambient temperature sensor failure
LED1
flash 13 times
Discharge temperature sensor failure
Indoor display
Outdoor display
Thermistor resistance check
Is it normal?
Yes
NO
Yes
Is it normal?
NO
Check the connector onnection
Replace the thermistor
Replace the indoor unit PCB
Correct the connection
8.5.
1 Thermistor or Related Abnormality
LED1 flash 14 times
Discharge temperature sensor failure
32
Summary of Contents for N Series
Page 11: ...Piping diagrams Domestic air conditioner Pinping diagrams 8...
Page 12: ...Operation range Domestic air conditioner 18 15 27 24 9 5 Operation range...
Page 27: ...Domestic air conditioner 24 Electrical Parts test...
Page 28: ...Domestic air conditioner 25...
Page 29: ...Domestic air conditioner 26...
Page 30: ...Domestic air conditioner 27 Electrical Parts test...
Page 31: ...Domestic air conditioner Seivice diagnosis...