The SubConnect module cannot use a wireless connection. 

 

It is important that each control linked to the network possesses the 
same network number (RF Network) as the address (RF Address) 
assigned to the unit coordinating the Wi-Farm network (coordinator). 

 

A total of 500 units may be connected in wireless mode. 

 

The total of units in both wired and wireless modes cannot exceed 500. 

 

3.

 

Configure sub-stations: 

If your installation includes SubConnect sub-

stations, follow activation steps described in each sub-station installation 
guide.

 

 

4.

 

Activate WebGate 3G module

: Connect the transformer into a wall outlet. 

Make sure the LCD display lights up. 

  

5.

 

Perform unit detection test

: This procedures goal is to initialize the 

WebGate 3G module and to verify its communication with the controls and 
SubConnect modules. You can find the navigation buttons provided for this 
purpose and an LCD display on the WebGate 3G faceplate. 

 

To access the installation menu, press and hold the “Select” button for about 3 
seconds. 

Warning, as long as the WebGate 3G is in installation mode, 

communication to the FarmQuest server is interrupted, therefore 
controls will no longer be checked. 

Once in the installation menu, use the 

“Menu” button to navigate through the installation menus. 
 
To view the number of units connected to the WebGate 3G, repeatedly press 
the “Menu” button until the display shows “Units Connected Total”. The total 
number of units appears on the second line of the LCD display. If there is a 
problem with one or more units, an exclamation point in brackets will appear 
alternating with a “Problems, See unit list” message. 
 
To view the “RF Address” of wireless units or the “Unit ID” of wired units 
and view (according to the situation) the details of problem units, when you 
see the total number of units, press the up or down arrows to scroll through all 
units connected to the WebGate 3G. 

 

What to do if the number of controls is incorrect? 

:  

Verify the list of controls detected. Each time the up or down arrow is pressed, 
the display will show the next unit found in ascending order. You will then be 
aware of the controls or SubConnect modules that were not detected. For the 
controls that were not detected, make the following verifications: 

-

 

In the case of a wired connection, verify that the “Unit ID” numbers 
have been correctly assigned on all controls and SubConnect 
modules. The WebGate module cannot detect units whose ID 
number is used on more than one control or SubConnect module. 

www.monitrol.com

Summary of Contents for WebGate 3G

Page 1: ...W WebG In Gate nstalla e 3G ation g Mo guide odule e www monitrol com...

Page 2: ...ds or modules consult the installation guide of the concerned product In this document only the WebGate 3G module will be presented in detail Below is a short description of cards and modules you may...

Page 3: ...installation example Below is a typical installation diagram demonstrating network hierarchy with different M2M products and the different ways the SubConnect can be linked to the WebGate 3G Figure 1...

Page 4: ...The package must contain the following standard items 1 WebGate 3G module with wireless RF IN card WEBGATE3G RF model or with wire connection NET IN2 card WEBGATE3G HW model 1 110V 5VDC wall transform...

Page 5: ...he module in a corridor to avoid exposing it to noxious gases Do not install the module directly in a breeding chamber To avoid condensation problems inside modules it is recommended to install the mo...

Page 6: ...ls C D It is not necessary that the WebGate 3G module be at the end of the loop Note that if the control is equipped with only 3 terminals A B C terminals C D of the WebGate 3G will be linked with a w...

Page 7: ...the Internet Use the included network cable with RJ 45 connector to link the WebGate 3G to an Internet access point Warning It is absolutely necessary that the communication equipment supports DHCP pr...

Page 8: ...rameter is used to adjust the communication channel The RF Channel parameter and is adjustable from OFF to deactivate the wireless function 1 to 16 The RF Network parameter allows the user to adjust t...

Page 9: ...controls will no longer be checked Once in the installation menu use the Menu button to navigate through the installation menus To view the number of units connected to the WebGate 3G repeatedly pres...

Page 10: ...WebGate or SubGate using a RS 485 cable check the wiring of the communication port labelled TO WEBGATE of the SubConnect module 6 Add guests by wireless connection Certain units have no interface ex...

Page 11: ...ng Check the network cable and make sure the Internet access equipment is powered up Make sure the link LED yellow on the Ethernet module is lit see figure 4 Make sure that the equipment used to estab...

Page 12: ...ication ports not at the end of a loop maintain continuity of the shielding by linking the drain wires 5 Ground the drainage wire of one control only The other extremity of the drainage wire must rema...

Page 13: ...eset Control terminal for Controlled AC Outlet module connection 3 5VDC power connector 4 RF IN wireless card connector 5 NET IN2 wired card connector 6 Ethernet module Link LED yellow ETHERNET RESET...

Page 14: ...to 131 F 20 C to 55 C Operation temperature 32 F to 122 F 0 C to 50 C Humidity 90 maximum non condensing Weight 1 4 lb 0 6 Kg Dimensions 6 x 6 x 3 3 4 15 cm x 15 cm x 9 5 cm Power supply Wall transfo...

Page 15: ...Unpacking 4 Equipment required for installation 4 Installation Steps 5 Activation Steps 8 Specifications 14 Limited Warranty 16 TABLE OF FIGURES Figure 1 Typical installation 3 Figure 2 Mounting 5 Fig...

Page 16: ...l or any other natural disaster Any unauthorized work modification or repair on this product automatically voids the warranty and disclaims the manufacturer from all responsibility The manufacturer as...

Reviews: