background image

© M2M Services, 1 Kukush Str, building M8, Sofia 1309, Bulgaria 

www.m2mservices.com

  

 

 
 

 

MQ03-LTE-M-FIRE 

Cellular Communicator 

with Dial Capture Interface 

 

Installation and Operation Manual 

Doc. No. 03002 V 1.1 08/2020 

 

 

Summary of Contents for MQ03-LTE-M-FIRE

Page 1: ...M Services 1 Kukush Str building M8 Sofia 1309 Bulgaria www m2mservices com MQ03 LTE M FIRE Cellular Communicator with Dial Capture Interface Installation and Operation Manual Doc No 03002 V 1 1 08 20...

Page 2: ...1 1 08 2020 2 M2M Services 2020 Table of Contents About this document 3 Product Description 5 Main Features 5 Specifications 6 Mounting and Wiring 7 Wiring the Communicator 7 Mounting the Communicato...

Page 3: ...s warranty does not cover any subscriber agreements or failure of services provided under the terms of such subscriber agreements or failure of cellular GPRS LAN or other related networks functions an...

Page 4: ...ety aware personnel Don t disassemble or refit the Device Do not attempt to personally repair it Mains power must be disconnected before any installation or tuning work starts The device installation...

Page 5: ...ommunication solution is a complete communication platform for data transfer from alarm systems at remote sites to Central Monitoring Stations CMS The platform allows bi directional data transmission...

Page 6: ...ions Supply Voltage 12 to 29 VDC Consumption Standby 50 mA Peak 200mA Frequency LTE CAT M1 700 850 1700 1900 2100 MHz GSM Providers AT T Verizon or other available in the area networks Dimensions 2 48...

Page 7: ...ted UL Listed UOJZ UTOU NBSX control panel or power supply The wiring should be done only when the panel is power down For Dry Indoor use only Wiring the Communicator The terminal strips can accommoda...

Page 8: ...nclosure or as an option any other UL Listed UOXX NITW or CYIV metal enclosure All the wiring must be routed through a conduit This enclosure shall have ample knockouts accommodating either or 1 condu...

Page 9: ...na to the box The antenna should be position perpendicular to the ground either right side up or upside down Try to keep the antenna away from sources of RF interference or where metal objects can shi...

Page 10: ...ata 6 Download the RControl Admin mobile application on your Android or IOS mobile device 7 Login with the end user credentials from the quick installation manual provided with the device For more det...

Page 11: ...uides for compatible alarm panels are available at http support m2mservices com panel programming Troubleshooting If you have issues receiving the events 1 Verify the RING TIP connection Make sure the...