result in short circuit, fire, malfunctions. FG Terminal must be used a dedicated ground. Not doing so 
could result in malfunctions. 
a. Grounding should be the Class 3 grounding. The cable for grounding should be more than 4㎟. 
b. grounding point be closed to the products and make short the distance to the ground cable if possible.  
Please see below.  

 
 
 
 
 
 
 
 

 
■ 

Installation Precautions

 

Do not install the location which exceeds allowed temperature. Product can be damaged or shorten 
the life. Especially Install environment as below should be avoided. 

 

Do not Install product to the place which the ambient temperature is out of limits, from 0℃ to 50℃ or on the 
surface of control board which high pressure equipment is installed. 
Do not install to the place where strong shock or vibration continuously have impacted on product.  
The space between back of product and back of control board must be more than 100mm for maintenance  
and ventilation.   
In order to improve water retention and ventilation, the space between the back of the main body 
and  the  console  box  should  be  100mm  or  more,  and  install  the  cooling  fan  when  installed  in  an 
enclosed space.

 

 

■  Disposal Precautions 

When  you  dispose  of  product  and  battery,  please  treat  it  as  industrial  waste.  It  can  create  poisonous 
substances or explosion.   

 

■  Cell Type Battery Specifications and Exchange 

Mounted on mainboard Model MS920SE Battery is not replaced by the user. If the battery has run out of 
service, please contact our Customer Support Center for replacement and inspection. 

 

  Item 

Content 

Battery Voltage 

DC 3V 

Battery Model 

MS920SE (lithium / Rechargeable ) 

Battery lifetime 

Permanent (In case of ambient temperature 25℃) 

Battery Discharge  Last about 7 days After turn it off 

*

 Depending on the model specifications are subject to change. 

 
■  All field-wiring connections to this unit shall be from Limited Voltage / Limited Current, below 24 Vdc 
isolated secondary source with an output fuse, or Class 2. 

Summary of Contents for TOPR Series

Page 1: ...82 70 465 3366 Fax 82 31 465 3355 www m2i co kr 1 18 Thank you for purchasing the industrial HMI touch panel series of M2I corporation Please read this manual carefully to know installing wiring oper...

Page 2: ...fications 7 3 1 Electrical Specifications 7 Chapter 4 Parts Identification and Functions 8 4 1 TOPRP Series 8 Chapter 5 External Device Interface 11 5 1 Serial Interface 11 5 2 Ethernet Communication...

Page 3: ...er into the front screen protective sheet The screen may be invisible or may cause a malfunction of the touch Use the radio or mobile phone at least 30cm away from the main unit Two or fewer bright sp...

Page 4: ...ion continuously have impacted on product The space between back of product and back of control board must be more than 100mm for maintenance and ventilation In order to improve water retention and ve...

Page 5: ...l control device required in industrial field It is a device based on RS 232C and RS 422 485 Ethernet which is used for the basic purpose of communication with another device PLC 2 2 Package Contents...

Page 6: ...of or special model D Display 10 10 2 10 4 V VGA 640 480 A AC Blank Non explosion proof or general model T P D 12 12 1 S SVGA 800 600 15 15 X XGA 1024 768 S for 12 1 model XGA 2 3 1 Process Module Mai...

Page 7: ...Memory Specifications Screen Memory 128MB Backup Memory 512KB System buffer 10K Word Including Alarm Log Recipe Backup Period Permanent Real Time Clock Built in by Battery 3 3 Environment Specificati...

Page 8: ...nual M2I Corporation 11 35 Simin daero 327beon gil Dongan gu Anyang si Gyeonggi do 14055 Korea Tel 82 70 465 3366 Fax 82 31 465 3355 www m2i co kr 8 18 Chapter 4 Parts Identification and Functions 4 1...

Page 9: ...Extension Module Connector Expansion module mounting cover 4 1 3 Side Part Names and Specifications TOPRP10 TOPRP20 No Part Form Description Etc USB HOST USB A type Connector for option for USB stora...

Page 10: ...r Plastic Cover SD Card Reset Switch Mode Switch included SD Card Socket SD Card Socket Data upload download Cover Sensor Photo coupler Cover open close detection Mode Switch DIP Switch 2P Set Up Syst...

Page 11: ...t NONE ODD EVEN Parity Stop Bit 1 2 bit Connector DSUB 9pin 5 1 2 RS 422 485 Items Contents Protocol Full Half Duplex Synch Asynchronous Communication Distance About 500M Type of connection 1 N N 31 C...

Page 12: ...1 D IN OUTPUT RS 485 Data 2 D IN OUTPUT RS 485 Data 3 SG Signal Ground Be sure to connect the RD and SD to the RS 232C communication line by crossing each other with a Twisted Pair Cable Please connec...

Page 13: ...d Control Bulk Transfer Speed 480Mb s Support Device USB Storage FAT16 FAT32 File Format Available Connector Type Type A 2ch 5 3 2 USB OTG Type Item Specification USB Interface USB 2 0 Communication M...

Page 14: ...ication Only TOPRP20 Type Item Specification Output specification Stereo audio output Connector Type 3 5mm Audio Plug Chapter 6 Installation Insert Process Module to Guide of Rear of Display Module an...

Page 15: ...TOPRPxxD TOPRPxxA 7 2 Ground wiring 1 The TOPR Panel has enough anti noise measure so except that there are many noises specially the ground is not needed When doing ground please refer to the followi...

Page 16: ...8 3 Problems with the Device a If there is a problem during operation stop using it and contact the A S department of M2I Corporation which is indicated on the product label b Only the authorized wor...

Page 17: ...s Module Hardware Manual M2I Corporation 11 35 Simin daero 327beon gil Dongan gu Anyang si Gyeonggi do 14055 Korea Tel 82 70 465 3366 Fax 82 31 465 3355 www m2i co kr 17 18 Chapter 9 Products and Warn...

Page 18: ...argeable lithium Battery Certificate Number Serial Number 10 2 DC Power Models Manufacture AS M2I Corporation 11 35 Simin daero 327beon gil Dongan gu Anyang si Gyeonggi do 14055 Korea Tel 82 31 465 33...

Reviews: