M-system W2XT Instruction Manual Download Page 3

W2XT

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5508  Rev.3  P. 3 / 4

EXTERNAL VIEWS

LED1 (LD1)

LED2 (LD2)

LED3 (LD3)

Configurator Jack

■ 

FRONT VIEW

■ 

SIDE VIEW

SW1

SW2

Output 2

Configuration DIP SW

Output 1

Configuration DIP SW

OFF

ON

1 2 3 4

OFF

ON

1 2 3 4

*

Provided only for two-output type.

*

OUTPUT RANGING

The internal DIP switch setting is required to select output 
types before setting a precise output range using PC Con-
figurator Software (model: W2CFG).
For detailed information on the PC configuration, refer to 
the W2CFG users manual.

Table 1. DIP switch setting: Output 1 type

OUTPUT 1 TYPE

SW1-1

SW1-2

SW1-3

SW1-4

0 – 20 mA DC

OFF

OFF

ON

OFF

-10 – +10 V DC

OFF

ON

OFF

ON

-5 – +5 V DC

ON

OFF

OFF

ON

Table 2. DIP switch setting: Output 2 type

OUTPUT 2 TYPE

SW2-1

SW2-2

SW2-3

SW2-4

0 – 20 mA DC

OFF

OFF

ON

OFF

-10 – +10 V DC

OFF

ON

OFF

ON

-5 – +5 V DC

ON

OFF

OFF

ON

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Check DIP switch setting.
3) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

4) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

  If the thermocouple or its extension wires are broken, the 

output goes over 100% (below 0% with downscale) due to 

burnout function.  Confirm the status indicator LED pat-

tern and check leadwires in such a case.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

6) LED:  Confirm that the LEDs indicate the normal operat-

ing mode.