CONNECTING THE VOS2T SIDE LEVER

Connect the lever to the VOS2T unit with a screw included 
in the package, with a plain washer and a toothed washer 
between them as in Figure 1.
Lever direction can be changed by 90 degrees.

 

CONNECTING THE VOS2T UNIT TO THE ACTUATOR

Set the VOS2T unit to the position where the VOS2T output 
is approximately 12mA with 50% actuator position (

θ

  = 0° 

in Figure 3), and where the VOS2T side lever and the actua-
tor side lever are positioned in a straight line.  See Figure 4 
below.  The actuator side lever should be threaded with the 
connecting pin but left loose.  Do not fix the connecting pin 
to the actuator side lever.

Diaphragm Actuator

Actuator Stem

Bracket

VOS2T

Lever, VOS2T Side

Lever, Acutator Side
(Clamp Set)

Figure 4

ELECTRICAL CONNECTIONS

Remove the VOS2T unit cover (or the terminal box cover 
with limit switch box option) and wire to the terminals ac-
cording to Figure 5.

15 – 28V DC

LOAD

+

OUTPUT

4 – 20mA DC

Figure 5

ADJUSTMENT PROCEDURE

Open the VOS2T unit cover.  Set the action direction* with 
jumpers (JP1, JP2 in Figure 1) and adjust Zero (Z) and Span 
(S) behind it.
*  Direct action: the output increases when the shaft turns 

clockwise (seen from the lever side). 
Reverse action: the output increases when the shaft turns 
counterclockwise (seen from the lever side).

 

HOW TO ADJUST ZERO AND SPAN

1) If you need reverse action, change the setting now.  Re-

move the cover and set the jumpers JP1 and JP2 to R 

position according to Figure 1.  Factory set zero point may 

be slided by changing the action direction.  Re-adjust ac-

cording to the following.

2) First operate the actuator 

slowly for full-stroke and 

check that the VOS2T out-

puts approximately 0 – 100% 

(4 – 20mA DC) accordingly.  

Be sure also that the output 

signal increases or decreases 

without interruption.

3) With 50% input (actuator 

position), check that the out-

put is approximately 50%. 

 

See Figure 6.

4) With 0% input, adjust the 

output to 0% with Zero ad-

justment.  See Figure 7.

5) Set the input to 100%.  If 

there is a deviation in out-

put signal, compensate half 

of the deviation via the Zero 

adjustment.  See Figure 8.

6) With 100% input, adjust the 

other half of the deviation 

with Span adjustment in or-

der to get 100% output.  See 

Figure 9.

7) Input 0%, 50% and 100% 

signals and check the output 

according to the respective 

input value.  If the output 

value is shifted, repeat the 

above procedure (3) – (6).

Note:  If you set a wider output span (narrower input span), 

the VOS2T does not output above or below the full-
scale range.

OUTPUT %

100

50

0

100
INPUT %

0

Fig. 6

OUTPUT %

100

50

0

100
INPUT %

0

Fig. 7

deviation

OUTPUT %

100

50

0

100
INPUT %

0

Fig. 8

1/2 deviation

OUTPUT %

100

50

0

100
INPUT %

0

Fig. 9

1/2 deviation