M-system Sentronic Mini-M Series Manual Download Page 5

M2ADS

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed specifications.

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1)  ZERO:   Apply  the  input  signals  which  should  lead  the 

calculated result as 0%, and adjust output to 0%.

2)  SPAN:  [K

1

 + K

2

 ≥ 1]  Apply the input signals which should 

lead the calculated result as 100%, and adjust output to 
100%.

  [K

1

 + K

2

 < 1]  Apply the input signals which should lead 

the  calculated  result  as  [100 

×

  (K

1

  +  K

2

)]%,  and  adjust 

output to [100 

×

 (K

1

 + K

2

)]%.

3)  Check ZERO adjustment again.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

EQUATION

  Output = K

1

 

×

 Input 1 + K

2

 

×

 Input 2

     

K

1

, K

2

: 0.10 to 2.00 specified when ordering

     

(0.40 ≤ K

1

 + K

2

)

     

Input 1, Input 2: 0 to 120%

     

Forcibly limited to 0% and 120% respectively when  

     

the signal is out of range.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.
[K

1

 + K

2

 ≥ 1]  Apply the input signals which should lead the 

calculated result as 0%, 25%, 50%, 75% and 100%.  Check 
that  the  output  signal  for  the  respective  input  signal  re-
mains within accuracy described in the data sheet.
[K

1

 + K

2

 < 1]  Apply the input signals which should lead the 

calculated result as 0%, [25 

×

 (K

1

 + K

2

)]%,  [50 

×

 (K

1

 + K

2

)]%,  

[75 

×

 (K

1

 + K

2

)]% and  [100 

×

 (K

1

 + K

2

)]%.  Check that the 

output signal for the respective input signal remains within 
accuracy described in the data sheet.
When the output is out of tolerance, recalibrate the unit ac-
cording  to  the  “ADJUSTMENT  PROCEDURE”  explained 
earlier.

EXTERNAL DIMENSIONS

  unit: mm (inch)

5

9

21.5 (.85)

70.5 (2.78)

84 (3.31)

10 (.39)

15 (.59)

6 (.23)

59 (2.32)

DIN RAIL
35mm wide

[4 (.16)]

8–M3

SCREW

72 (2.83)

23 (.91)

2–4.2x5

(.17x.20)

MTG HOLE

6 (.24) deep

114 (4.49)

• When mounting, no extra space is needed between units.

4

8

12

14 13

1

4 (.16)

1

4

+

INPUT 1

5

8

+

INPUT 2

+

OUTPUT

9

12

U(+)

V(–)

POWER

13

14

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com