M2ADS
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
13 – 14 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply the input signals which should lead the
calculated result as 0%, and adjust output to 0%.
2) SPAN: [K
1
+ K
2
≥ 1] Apply the input signals which should
lead the calculated result as 100%, and adjust output to
100%.
[K
1
+ K
2
< 1] Apply the input signals which should lead
the calculated result as [100
×
(K
1
+ K
2
)]%, and adjust
output to [100
×
(K
1
+ K
2
)]%.
3) Check ZERO adjustment again.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
EQUATION
Output = K
1
×
Input 1 + K
2
×
Input 2
K
1
, K
2
: 0.10 to 2.00 specified when ordering
(0.40 ≤ K
1
+ K
2
)
Input 1, Input 2: 0 to 120%
Forcibly limited to 0% and 120% respectively when
the signal is out of range.
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes.
[K
1
+ K
2
≥ 1] Apply the input signals which should lead the
calculated result as 0%, 25%, 50%, 75% and 100%. Check
that the output signal for the respective input signal re-
mains within accuracy described in the data sheet.
[K
1
+ K
2
< 1] Apply the input signals which should lead the
calculated result as 0%, [25
×
(K
1
+ K
2
)]%, [50
×
(K
1
+ K
2
)]%,
[75
×
(K
1
+ K
2
)]% and [100
×
(K
1
+ K
2
)]%. Check that the
output signal for the respective input signal remains within
accuracy described in the data sheet.
When the output is out of tolerance, recalibrate the unit ac-
cording to the “ADJUSTMENT PROCEDURE” explained
earlier.
EXTERNAL DIMENSIONS
unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
84 (3.31)
10 (.39)
15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.