WIRING INSTRUCTIONS
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable.
• M3 Screw (current input)
Applicable wire size: 0.25 to 1.65 mm
2
(AWG22 to 16)
Torque: 0.5 N∙m
3.3 max. (.13)
6 max.
(.24)
mm (inch)
• M3.5 Screw (auxiliary power and voltage input)
Applicable wire size: 1.04 to 2.63 mm
2
(AWG16 to 14)
Torque: 0.8 N∙m
3.8 max. (.15)
7 max.
(.28)
mm (inch)
CHECKING ETHERNET CONNECTION
■
IP ADDRESS
The R9EWTU does not support BootP Table Software. The IP Address and Subnet Mask can be configured using the PMCFG
Configurator Software.
The Modbus/TCP Port No. is fixed at 502.
■
NODE ADDRESS
The R9EWTU firmware sets its Node Address to “01.”
The Node Address (ID) is sent via Modbus together with data. Set “01” with the application software of the user.
■
CHECK WIRING
Connect an Ethernet cable to the RJ-45 connector.
■
CHECK LED
When wiring is correct, LINK LED is turned on with 10BASE or 100BASE link.
When the module is receiving data with 100BASE, LK100 LED blinks.
■
CHECK R9EWTU CONNECTION
Enter “ping command” on the Windows MS-DOS as follows:
C:¥WINDOWS>ping ***.***.***.***
(***.***.***.***: Enter IP address in decimal.)
ping ***.***.***.*** with 32 bytes of data:
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Ping statistics for ***.***.***.***
Packets:Sent=4,Received=4,Lost=0(0% loss)
Replies in case of normal connection are as shown above. If the connection cannot be established normally due to e.g. wrong
IP address, other replies such as ‘time out’ will be received.