R8-YVM4N
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-9672 P. 4 / 6
• Configuration Mode: SW4-8
CONFIGURATION MODE
SW4-8
DIP switch setting (*)
OFF
PC Configurator and communication
ON
Note 2: Be sure to set unused SW4-3 through 4-6 to OFF.
■
TERMINATOR DIP SW: SW3
TERMINATOR SW
SW3
Without (*)
OFF
With
ON
PC CONFIGURATOR
The following parameter items can be configured with PC Configurator Software (model: R8CFG).
Refer to the users manual of the software for detailed operations.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RAGNE
DEFAULT SETTING
Output range
-10 - 10 V DC
-10 - +10 V DC
Lower range value
-10.00 - +10 00 (V)
-10.00 (V)
Upper range value
-10.00 - +10 00 (V)
10.00 (V)
Fine zero adjustment
-320.00 - +320.00 (%)
0.00 (%)
Fine gain adjustment
-3.2000 - +3.2000
1.0000
Scaled range Zero
-32000 - +32000
0
Scaled range Span
-32000 - +32000
10000
Initial output at the startup (scaled range)
-32000 - +32000
0
Fixed output at the loss of comunication (scaled range)
-32000 - +32000
-500
■
CHANNEL BATCH SETTING
PARAMETER
SETTING RAGNE
DEFAULT SETTING
Loss of internal bus communication detection time
0.0 – 99.9 (sec.)
1.0 (sec.)
Output function at the loss of communication
Hold the last normally received data
Fixed output as specified
Hold the last normally
received data
Configuration mode
DIP SW (OFF)
PC (ON)
DIP SW (OFF)
Note. Be sure to set SW4-8 to ON to configure output range and output at the loss of communication by the PC configurator.
Settings are programmed by the PC Configurator via the Power/Network Module.