• Configuration Mode: SW4-8

CONFIGURATION MODE

SW4-8

DIP switch setting (*)

OFF

PC Configurator and communication

ON

Note 2: Be sure to set unused SW4-3 through 4-6 to OFF.

 

TERMINATOR DIP SW: SW3

TERMINATOR SW

SW3

Without (*)

OFF

With

ON

PC CONFIGURATOR

The following parameter items can be configured with PC Configurator Software (model: R8CFG).
Refer to the users manual of the software for detailed operations.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RAGNE

DEFAULT SETTING

Output range

-10 - 10 V DC

-10 - +10 V DC

Lower range value

-10.00 - +10 00 (V)

-10.00 (V)

Upper range value

-10.00 - +10 00 (V)

10.00 (V)

Fine zero adjustment

-320.00 - +320.00 (%)

0.00 (%)

Fine gain adjustment

-3.2000 - +3.2000

1.0000

Scaled range Zero

-32000 - +32000

0

Scaled range Span

-32000 - +32000

10000

Initial output at the startup (scaled range)

-32000 - +32000

0

Fixed output at the loss of comunication (scaled range)

-32000 - +32000

-500

 

CHANNEL BATCH SETTING

PARAMETER

SETTING RAGNE

DEFAULT SETTING

Loss of internal bus communication detection time

0.0 – 99.9 (sec.)

1.0 (sec.)

Output function at the loss of communication

Hold the last normally received data
Fixed output as specified

Hold the last normally 
received data

Configuration mode

DIP SW (OFF)
PC (ON)

DIP SW (OFF)

Note. Be sure to set SW4-8 to ON to configure output range and output at the loss of communication by the PC configurator.

Settings are programmed by the PC Configurator via the Power/Network Module.