PC CONFIGURATOR

The following parameter items can be configured with PC Configurator Software (model: R8CFG).
Refer to the users manual of the software for detailed operations.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Input Range

-20 to +20 (mA DC)

-20 to +20 (mA DC)

Lower range value

-20.00 to +20.00 (mA)

4.00 (mA)

Upper range value

-20.00 to +20.00 (mA)

20.00 (mA)

Fine zero adjustment

-320.00 to +320.00 (%)

0.00 (%)

Fine gain adjustment

-3.2000 to +3.2000

1.0000

Scaled range Zero

-32000 to +32000

0

Scaled range Span

-32000 to +32000

10000

 

CHANNEL BATCH SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Loss of internal bus communication detection time

0.0 to 99.9 (sec.)

1.0 (sec.)

Input moving average

Disable / Enable (8 times)

Disable

Configuration mode

DIP switch (OFF), 
PC (ON)

DIP switch (OFF)

Note: Turn SW2-8 ON to allow programming by the PC Configurator via the Power/Network Module.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

24 (.94)

72 (2.83)

115 (4.53)

6 (.24)

7 (.28)

6 (.24)

7 (.28)

DIN RAIL
(35 mm wide)

[3 (.12)]

[4 (.16)]

55 (2.17)

Summary of Contents for R8-SVT8

Page 1: ...the power supply and input signal for safety Do not touch the connector while the power is supplied Static electricity may cause a malfunction Switches on the side of the module can be set for mainte nance only while the power supply is off Do not access them while the power is supplied ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper ...

Page 2: ...d slide it straight until the hooks are latched When removing the cover pull it out while squeezing the hooks inward Groove Hook HOW TO UNMOUNT THE MODULE ON DIN RAIL Release the locking clamps and pull out straight the module Caution 1 Be careful not to hurt your hand by pointed edges of the internal bus connector 2 I O modules cannot hold tightly on the DIN rail by themselves without power netwo...

Page 3: ...nput 4 9 In5 Input 5 10 Input 5 11 In6 Input 6 12 Input 6 13 In7 Input 7 14 Input 7 15 In8 Input 8 16 Input 8 MODULE ADDRESS SW1 SW1 1 through 1 4 determine the tenth place digit while SW1 5 through 1 8 do the ones place digit of the module address Address is selected between 0 to 28 Factory setting 0 MODULE ADDRESS SW1 10 1 2 3 4 1 5 6 7 8 0 OFF OFF OFF OFF 1 OFF OFF OFF ON 2 OFF OFF ON OFF 3 OFF...

Page 4: ... to 20 00 mA 20 00 mA Fine zero adjustment 320 00 to 320 00 0 00 Fine gain adjustment 3 2000 to 3 2000 1 0000 Scaled range Zero 32000 to 32000 0 Scaled range Span 32000 to 32000 10000 CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Loss of internal bus communication detection time 0 0 to 99 9 sec 1 0 sec Input moving average Disable Enable 8 times Disable Configuration mode DIP switc...

Page 5: ... CONNECTOR EXC SUPPLY 1 INTERNAL POWER 1 Not used WIRING INSTRUCTIONS TENSION CLAMP TERMINAL BLOCK Unit side connector MC1 5 16 GF 3 5 Phoenix Contact Cable side connector FMC1 5 16 STF 3 5 Phoenix Contact Applicable wire size 0 2 1 5 mm2 Stripped length 10 mm Recommended solderless terminal AI0 25 10YE 0 25 mm2 Phoenix Contact AI0 34 10TQ 0 34 mm2 Phoenix Contact AI0 5 10WH 0 5 mm2 Phoenix Contac...

Reviews: