M-system R8-DCM16ALZ Instruction Manual Download Page 4

R8-DCM16ALZ

P. 4 / 5

EM-9748 Rev.1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

 FULL INTERLOCK FUNCTION

It is available to apply full interlock function to all outputs 
(Do1 through Do16)

Full Interlock Function

SW3-1

OFF

OFF

ON (*) (all outputs OFF if input OFF)

ON

Caution: SW3-2 is unused; be sure to turn OFF unused 

channels.

 PC CONFIGURATOR

The following parameters can be set with using PC Configu-

rator Software (model: R8CFG):
• Output at the startup
• Output at the loss of communication
• Common setting (loss of internal bus communication de

-

tection time)

Turn SW2-8 ON to allow programming by the PC Configu

-

rator via the Power / Network Module.

Refer to the users manual of the R8CFG for detailed opera

-

tion of the software program.

 MODULE ADDRESS

Module address can be set with SW1-1 through 1-4 for the 
tens, and SW1-5 through 1-8 for the ones place digit.  
Address is selected between 0 to 31.  (Factory setting: 0)

MODULE ADDRESS

SW1

1

5

2

6

3

7

4

8

0

OFF

OFF

OFF

OFF

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

OFF

ON

OFF

OFF

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

8

ON

OFF

OFF

OFF

9

ON

OFF

OFF

ON

 OPERATING MODE

*Factory setting

• Interlock Communication Logic Reversal

Setting internal communication bus logic.

Interlock Communication Logic Reversal

SW2-1

Interlock function setting off: 1
Interlock function setting on: 
normal = 1, interlock = 0 

ON

Interlock function setting off: 0 (*)
Interlock function setting on: 
normal = 0, interlock = 1 

OFF

Caution: 1 and 0 values are validated as logic through 

internal communication bus logic. 

• Output at The Loss of Communication

Setting for all output.

OUTPUT AT THE LOSS OF COMMUNICATION

SW2-5

Output Hold (*) (last data correctly rerceived 

is hold

OFF

Stop output (Output fixed at OFF)

ON

• Terminator DIP SW

TERMINATOR SW

SW2-6

Without (*)

OFF

With

ON

 

• Configuration Mode

CONFIGURATION MODE

SW2-8

DIP switch setting (*)

OFF

PC Configurator and communicaton

ON

Caution: SW2-2 through 2-4 and 2-7 are unused; be sure to 
turn OFF unused channels.