background image

R7M-EC16B

P.  / 6

EM-7803-K Rev.3

PNP TRANSISTOR OUTPUT EXTENSION MODULE, 16 points

(Modbus)

MODEL

R7M-EC16B

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If  you  have  any  problems  or  questions  with  the  product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Discrete output extension module ............................... (1)

 MODEL NO.

Confirm  Model  No.  marking  on  the  product  to  be  exactly 
what you ordered.

 INSTRUCTION MANUAL

This  manual  describes  necessary  points  of  caution  when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 NONINCENDIVE APPROVAL OPTION

• This equipment is suitable for use in Class I, Division 2, 

Groups A, B, C, D or Non-Hazardous Locations only.

• WARNING! – Explosion Hazard –
  Substitution of any component may impair suitability for 

Class I, Division 2.

• WARNING! – Explosion Hazard –
  DO NOT disconnect while the circuit is live or unless the 

area is known to be free of ignitable concentrations.

• Temperature Code of this equipment is T5 and the Maxi-

mum  Ambient  Temperature  is  55°C  (Surrounding  Tem-
perature inside the fire enclosure).

 CONFORMITY WITH UL APPROVAL

• This equipment is suitable for use in Installation Catego-

ry II and in a Pollution Degree 2 environment.

• Altitude up to 2000 meters
• This  equipment  must  be  mounted  inside  a  suitable  fire 

enclosure.

• This equipment is to be supplied by a Class 2 power sup-

ply.

 CONFORMITY WITH EC DIRECTIVES

• The  equipment  must  be  mounted  inside  the  instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations,  connected  devices  and  connected  wires  may 
affect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 WIRING

• Do  not  install  cables  (power  supply,  input  and  output) 

close  to  noise  sources  (relay  drive  cable,  high  frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying  complete  performance  described  in  the  data 
sheet.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7M-EC16B

Page 1: ...be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EC DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this unit when it is integrated in a panel syst...

Page 2: ...Indicator LED Output Terminals OUTPUT TERMINAL ASSIGNMENT DISCRETE I O STATUS INDICATOR LED Discrete I O modules including those for extensions have LED indicators showing I O signal status Contact ON LED ON Contact OFF LED OFF 10 24V 11 Y1 12 Y3 1 0V 2 Y0 3 Y2 13 Y5 4 Y4 14 Y7 5 Y6 15 Y9 6 Y8 16 YB 7 YA 17 YD 8 YC 9 YE 18 YF NO ID FUNCTION NO ID FUNCTION 1 0V 0V 10 24V 24V DC common 2 Y0 Output 0...

Page 3: ...t of the control panel Choose a thick and short cable to ground the FG terminal of the R7M module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases by grounding the FG terminal remove the grounding When painting the internal plate of the control panel apply masking to expose metal surface to secure conductivity at the sections where the follow...

Page 4: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7M Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Page 5: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the imp...

Page 6: ...T AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE M SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 06 6659 8201 Fax 06 6659 8510 E mail info m system co jp Noise Filter M...