background image

R7M-DAC16D

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7803-AL  Rev.4  P. 3 / 8

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

6

7

1

2

3

DG +24V

0V

DB

SLD

FG

(1)  DB 

(2)  SLD 

Shield

(3)  FG 

FG

(4)  DA 

(5)  DG 

(6)  +24V 

Power input (24V DC)

(7)  0V 

Power input (0V)

 

I/O TERMINAL ASSIGNMENT

14

5

6

X7

X6

Y0

15

Y1

16

17

18

7

8

9

Y3

Y5

Y7

Y2

Y4

10

1

2

C+

C–

X0

11

X1

12

13

3

4

X3

X5

X2

X4

Y6

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

C–

Common–

10

C+

2

X0

Input 0

11

X1

Input 1

3

X2

Input 2

12

X3

Input 3

4

X4

Input 4

13

X5

Input 5

5

X6

Input 6

14

X7

Input 7

6

Y0

Output 0

15

Y1

Output 1

7

Y2

Output 2

16

Y3

Output 3

8

Y4

Output 4

17

Y5

Output 5

9

Y6

Output 6

18

Y7

Output 7

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate. 
(Factory setting: OFF)

 

EXTENSION MODULE

Combinations with all extension modules are available.

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R7CON for detailed operation.

 

INTERFACE MODULE SETTING 

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

1.0 (sec.) 

Data Mode

RTU / ASCII

RTU

Parity

NONE / ODD / EVEN

NONE

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Output Operation Mode

Maintained / Momentary

----

Summary of Contents for R7M-DAC16D

Page 1: ...TIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 40mA GENERAL PRECAUTIONS Before you remove the unit or...

Page 2: ...s place digit of the address 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Node Address Setting x1 Factory setting 00 Node Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch Factory...

Page 3: ...13 X5 Input 5 5 X6 Input 6 14 X7 Input 7 6 Y0 Output 0 15 Y1 Output 1 7 Y2 Output 2 16 Y3 Output 3 8 Y4 Output 4 17 Y5 Output 5 9 Y6 Output 6 18 Y7 Output 7 TERMINATING RESISTOR To use the terminating...

Page 4: ...5 20 3 12 5 5 22 DIN RAIL 35 mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for Modbus POWER 18 M3 SCREW TERMINALS for I O 6 24 6 24 CONNECTION DIAGRAM Note In order to improve E...

Page 5: ...OFF ON ON Y0 MOMENTARY OUTPUT MODE Y0 and Y1 Y2 and Y3 Y4 and Y5 Y6 and Y7 are respectively combined to realize momentary switching with one shot output Bit 0 2 4 6 are used to control each set of out...

Page 6: ...4 Unused 15 Unused Momentary Output Mode BIT OUTPUT DATA STATE 0 Y0 1 One shot output Y1 0 One shot output 1 Unused 2 Y2 1 One shot output Y3 0 One shot output 3 Unused 4 Y4 1 One shot output Y5 0 One...

Page 7: ...ultiple Registers General purpose register within the slave read write 17 Report Slave ID Slave type RUN status Exception Codes CODE NAME 01 Illegal Function Function code is not allowable for the sla...

Page 8: ...Rev 4 P 8 8 WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable w...

Reviews: