background image

R7L-SV4

EM-7804-A  Rev.5  P. 6 / 18

• Configuration Properties

CONFIGURATION
PROPERTY

NETWORK 
VARIABLE

TYPE
{ Range }
{ Default }

EXPLANATIONS

SCPTdirection

----

{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}

Bit 0, Bit 1: Setting the extension module (Power supply 
must be reset when this configuration property is changed.)
0,0 : Without extension module
1,0 : Discrete input (fb and other settings assigned to the 9th 
and following points are invalid with 8-point input module.)
0,1 : Discrete output (fb and other settings assigned to the 
9th and following points are invalid with 8-point output 
module.)
Set this property before an extension module is connected.
Bit 2 through Bit 15 : Invalid

SCPTmaxSendTime
[Number of fb]

----

{SNVT_time_sec}
{0.0,10.0...3600.0}
{0.0}

Maximum time interval to send network variables (per fb).  
(Power supply must be reset when this configuration prop-
erty is changed.)
Network variables are sent out in the specified intervals 
even when there is no change in the value.
No sending when a value less than 10.0 is set.
Invalid property when the assigned fb has no network vari-
ables to be sent to the network.

SCPTminSendTime
[Number of fb]

----

{SNVT_time_sec}
{0.0,0.2...3600.0}
{1.0}

Minimum time interval to send network variables (per fb).  
(Power supply must be reset when this configuration prop-
erty is changed.)
Network variables are sent out in the specified intervals 
even when there are changes in the value faster than the 
interval.
No sending when a value less than 0.2 is set.
Invalid property when the assigned fb has no network vari-
ables to be sent to the network.

SCPTlocation

----

{SNVT_str_asc}
{30-character string}
{“”}

Used to write Tag No. (name)

SCPToemType

----

{SNVT_str_asc}
{e.g. “R7L-SV4_VER:0.10”}

Used to indicate Model No. and Version

SCPTserialNumber

----

{SNVT_str_asc}
{e.g. “ZZ123456”}

Used to indicate Serial No.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7L-SV4-R

Page 1: ...ating marked on the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60 Hz approx 80mA 24V DC rating 24V 10 approx 50mA GENERAL PRECAUTIONS Before you remove the un...

Page 2: ...tch behind the front cover to reset Control functions are halted while completing resetting and restarting Confirm no danger before conducting resetting POWER SUPPLY LONWORKS TERMINAL ASSIGNMENT 4 NET...

Page 3: ...TERMINALS for INPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG NET2 NET2 NET1 NET1 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12 VL1 13 I1 4 COM1 INPUT 1 6 VH2 15 VL2 16 I2 7 COM2 INPUT 2 8 VH3 17...

Page 4: ...NAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Reco...

Page 5: ...dicate Serial No NodeObject Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviRequest SNVT_obj_request For use with LonMaker and other to...

Page 6: ...is configuration prop erty is changed Network variables are sent out in the specified intervals even when there is no change in the value No sending when a value less than 10 0 is set Invalid property...

Page 7: ...TinvrtOut nviCNTCtrl SCPTpwrUpState nvoCNTOut SCPTnvType SCPTmaxRnge SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCNTIn...

Page 8: ...TIn 50 ms for the input terminals DO NOT connect a network variable to nviCNTIn when one of the input terminals other than nviCNTIn is assigned as the counted object ON time per 1 second increments SC...

Page 9: ...1 00 to 5 00 V 6 0 00 to 1 00 V 7 0 500 to 0 500 V 8 0 000 to 0 500 V 9 20 00 to 20 00 mA 10 4 00 to 20 00 mA 11 0 00 to 20 00 mA SCPTsndDelta nvoSVVal SNVT_lev_cont 0 100 100 000 1 0 Minimum deviatio...

Page 10: ...s SCPTnvType SCPTsetpoint nvoCVOut SCPTnvType SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCVIn SNVT_lev_percent 163 84...

Page 11: ...type For use with LonMaker and other tools SCPTnvType nvoCVOut SNVT_nv_type SNVT_temp Indicates nvoCVOut type For use with LonMaker and other tools SCPTsetpoint 0 nviCVIn Same as nviCVIn Scaling sett...

Page 12: ...27 66 0 0 SNVT_count_32 0 999 999 999 0 Inputs the value to be compared to the alarm setpoint nvoARM1 SNVT_switch 0 0 0 100 0 1 0 0 1 nviARMIn alarm 1 HH 100 0 1 with nviARMIn SCPTsetpoint 0 Reset to...

Page 13: ...ls SCPTsetpoint 0 nviARMIn SNVT_lev_percent 163 840 163 835 80 000 SNVT_temp 274 0 6279 5 80 0 SNVT_temp_p 273 17 327 66 80 00 SNVT_count_32 0 999 999 999 10 000 Alarm 1 nvoARM1 setpoint SCPTsetpoint...

Page 14: ...v 92 nv 93 nv 94 nv 95 nv 108 Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviLEDState SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 The front LEDs 0 F turn on off according...

Page 15: ...EX1 status Y1 Y3 Y5 Y7 Y9 YB YD YF Output nviDOEX2 status nv 4 nv 11 nviDOEX1 SNVT_switch nv 12 nv 19 nviDOEX2 SNVT_switch Output Terminal v s fbDOEX Network Variables nviDOEX1 nviDOEX2 Assignments FU...

Page 16: ...Other OFF Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 1 Output held or not at p...

Page 17: ...IEX2 Combination Mode Refer to the table in the next page fbDIEX SCPTdirection nvoDIEX1 SCPTinvrtOut nvoDIEX2 SCPTinvrtOut Set operating mode Invert output Invert output Input Terminal v s fbDIEX Netw...

Page 18: ...0 1 ON Invalid OFF ON 0 0 0 OFF 0 0 0 OFF ON ON 100 0 1 ON 100 0 1 ON nvoDIEX2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Defa...

Reviews: