background image

R7L-RS4

EM-7804-C  Rev.5  P. 17 / 19

 

FUNCTIONAL BLOCK: fbDOEX[0...7]

• Network Properties

NETWORK
VARIABLE

TYPE
{ Range }
{ Default }

EXPLANATIONS

nviDOEX1

{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}

Turns on or off  Y0, Y2, Y4, Y6, Y8, YA, YC, YE of the extension module 
depending upon this input.
100.0 1 : ON
Other : OFF

nviDOEX2

{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}

Turns on or off  Y1, Y3, Y5, Y7, Y9, YB, YD, YF of the extension module 
depending upon this input.
100.0 1 : ON
Other : OFF

• Configuration Properties

CONFIGURATION
PROPERTY

NETWORK 
VARIABLE

TYPE
{ Range }
{ Default }

EXPLANATIONS

SCPTdirection

----

{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}

Bit 1: Output held or not at power off
0 : OFF at the power startup
1 : Outputs the held status at the power startup
Bit 0, Bit 2 through 15 : Invalid

SCPTpwrUpState

nviDOEX1

{SNVT_switch}
{0.0 0}, {100.0 1},
{Invalid}
{0.0 0}

Set value applied at nviDOEX1 when the power supply is 
turned on.

SCPTpwrUpState

nviDOEX2

{SNVT_switch}
{0.0 0}, {100.0 1},
{Invalid}
{0.0 0}

Set value applied at nviDOEX2 when the power supply is 
turned on.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7L-RS4-R

Page 1: ...the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60 Hz approx 85mA 24V DC rating 24V 10 approx 50mA GENERAL PRECAUTIONS Before you remove the unit or mount it...

Page 2: ...Used to identify the node in LONWORKS network configura tion RESET SWITCH Used to reset the Neuron Chip Press the switch behind the front cover to reset Control functions are halted while completing...

Page 3: ...0 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for LONWORKS POWER 18 M3 SCREW TERMINALS for INPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG NET2 NET2 NET1 NET1 10 INA0 Input Connection Example I...

Page 4: ...NAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Reco...

Page 5: ...d Version Indicate Serial No NodeObject Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviRequest SNVT_obj_request For use with LonMaker...

Page 6: ...is configuration prop erty is changed Network variables are sent out in the specified intervals even when there is no change in the value No sending when a value less than 10 0 is set Invalid property...

Page 7: ...TinvrtOut nviCNTCtrl SCPTpwrUpState nvoCNTOut SCPTnvType SCPTmaxRnge SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCNTIn...

Page 8: ...TIn 50 ms for the input terminals DO NOT connect a network variable to nviCNTIn when one of the input terminals other than nviCNTIn is assigned as the counted object ON time per 1 second increments SC...

Page 9: ...mbr nvoRSVal SCPTnvType SCPTminDeltaTemp SCPToffset SCPTdefScale SCPTsetpoint nvoRSPVal SCPToffset SCPTgain Network Variables Configuration Properties RTD input Input 0 Input 1 Input 2 Input 3 Network...

Page 10: ...SCPToffset 0 SCPTsetpoint 0 nvoRSVal Same as nvoRSVal nvoRSVal lower range temperature SCPTsetpoint 0 SCPTsetpoint 1 SCPTsetpoint 1 nvoRSVal Same as nvoRSVal nvoRSVal upper range temperature SCPTsetpo...

Page 11: ...s SCPTnvType SCPTsetpoint nvoCVOut SCPTnvType SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCVIn SNVT_lev_percent 163 84...

Page 12: ...type For use with LonMaker and other tools SCPTnvType nvoCVOut SNVT_nv_type SNVT_temp Indicates nvoCVOut type For use with LonMaker and other tools SCPTsetpoint 0 nviCVIn Same as nviCVIn Scaling sett...

Page 13: ...27 66 0 0 SNVT_count_32 0 999 999 999 0 Inputs the value to be compared to the alarm setpoint nvoARM1 SNVT_switch 0 0 0 100 0 1 0 0 1 nviARMIn alarm 1 HH 100 0 1 with nviARMIn SCPTsetpoint 0 Reset to...

Page 14: ...ls SCPTsetpoint 0 nviARMIn SNVT_lev_percent 163 840 163 835 80 000 SNVT_temp 274 0 6279 5 80 0 SNVT_temp_p 273 17 327 66 80 00 SNVT_count_32 0 999 999 999 10 000 Alarm 1 nvoARM1 setpoint SCPTsetpoint...

Page 15: ...bles Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviLEDState SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 The front LEDs 0 F turn on off according...

Page 16: ...EX1 status Y1 Y3 Y5 Y7 Y9 YB YD YF Output nviDOEX2 status nv 4 nv 11 nviDOEX1 SNVT_switch nv 12 nv 19 nviDOEX2 SNVT_switch Output Terminal v s fbDOEX Network Variables nviDOEX1 nviDOEX2 Assignments FU...

Page 17: ...Other OFF Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 1 Output held or not at p...

Page 18: ...IEX2 Combination Mode Refer to the table in the next page fbDIEX SCPTdirection nvoDIEX1 SCPTinvrtOut nvoDIEX2 SCPTinvrtOut Set operating mode Invert output Invert output Input Terminal v s fbDIEX Netw...

Page 19: ...0 1 ON Invalid OFF ON 0 0 0 OFF 0 0 0 OFF ON ON 100 0 1 ON 100 0 1 ON nvoDIEX2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Defa...