background image

R7L-RR8

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7804-T  Rev.6  P. 2 / 14

COMPONENT IDENTIFICATION

ERR

SVCE

ONLINE

TX/RX

PWR

0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

Reset SW

Factory Configuration Port

Service SW

Status Indicator LED

I/O Status Indicator LED

L

ON

W

ORKS

, Power Supply

Terminals

Output Terminals

 

STATUS INDICATOR LED

ID

COLOR

STATE

MEANING

PWR

Green

ON

Internal 5V is normal

OFF

Internal 5V is abnormal.

ONLINE Green

ON

Online

Blink

approx.

0.5 Hz

Offline
Sending/receiving of Net-
work
Variables has stopped.

Blink

approx.

2 Hz

Receiving Wink Message

OFF

Abnormal state

ERR

Red

ON

Writing in the non-volatile 
memory

Blink

Abnormal state

OFF

Normal state

TX/RX

Green

ON

Sending/receiving Network 
Variables

OFF

Communication is lost.

SVCE

Green

ON

No network information

Blink

approx.

0.5 Hz

Offline
Sending/receiving of Net-
work
Variables has stopped.

OFF

Normal state

 

I/O STATUS INDICATOR LED

Output and feedback input status are indicated with LED.
     

ON  

: LED ON

     

OFF  : LED OFF

 

SERVICE SWITCH

Used to identify the node in L

ON

W

ORKS

 network configura-

tion.

 

RESET SWITCH

Used to reset the Neuron Chip.  Press the switch behind the 
front cover to reset.
Control functions are halted while completing resetting and 
restarting.  Confirm no danger before conducting resetting.

 

POWER SUPPLY, L

ON

W

ORKS

 TERMINAL ASSIGNMENT

4

NET1

5

NET2

6

U (+)

1

NET1

2

NET2

3

FG

7

V (–)

NO.

ID

FUNCTION, NOTES

1

NET1

L

ON

W

ORKS

 communication 1

2

NET2

L

ON

W

ORKS

 communication 2

3

FG

FG

4

NET1

L

ON

W

ORKS

 communication 1

5

NET2

L

ON

W

ORKS

 communication 2

6

U (+)

Power input

7

V (–)

Power input

Note:   L

ON

W

ORKS

 wiring must be paired between NET1 termi-

nals and/or NET2 terminals.

 

OUTPUT TERMINAL ASSIGNMENT

10

NC

11

Y0

12

Y1

1

NC

2

C0

3

C1

13

Y2

4

C2

14

Y3

5

C3

15

Y4

6

C4

16

Y5

7

C5

17

Y6

8

C6

9

C7

18

Y7

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

10

NC

No connection

2

C0

Common 

11

Y0

Output 0

3

C1

Common 

12

Y1

Output 1

4

C2

Common 

13

Y2

Output 2

5

C3

Common

14

Y3

Output 3

6

C4

Common

15

Y4

Output 4

7

C5

Common 

16

Y5

Output 5

8

C6

Common 

17

Y6

Output 6

9

C7

Common 

18

Y7

Output 7

Summary of Contents for R7L-RR8

Page 1: ...RECAUTIONS Before you remove the unit or mount it turn off the power supply and output signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the un...

Page 2: ...stopped OFF Normal state I O STATUS INDICATOR LED Output and feedback input status are indicated with LED ON LED ON OFF LED OFF SERVICE SWITCH Used to identify the node in LONWORKS network configura t...

Page 3: ...1 2 3 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 3 12 5 5 22 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for LONWORKS POWER 18 M3 SCREW TERMINALS for OUTPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2...

Page 4: ...NNECTION HOST PC LONWORKS R7L LONWORKS R7L LONWORKS Terminator WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal siz...

Page 5: ...oemType SCPTserialNumber Extension module setting Maximum sending time per fb Minimum sending time per fb Set Tag No name Indicate Model No and Version Indicate Serial No NodeObject Network Variables...

Page 6: ...0 0 Maximum time interval to send network variables per fb Power supply must be reset when this configuration prop erty is changed Network variables are sent out in the specified intervals even when...

Page 7: ...NTOut Set the maximum count Set the value when fbCNT is reset fbCNT SCPTdirection nviCNTIn SCPTinvrtOut nviCNTCtrl SCPTpwrUpState nvoCNTOut SCPTnvType SCPTmaxRnge SCPTsetpoint Network Variables Config...

Page 8: ...1 Count always reset to 0 Bit 5 8 through 15 Invalid Minimum input pulse width 500 ms for nviCNTIn 50 ms for the input terminals DO NOT connect a network variable to nviCNTIn when one of the input ter...

Page 9: ...CMPIn2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Connects to the network variable to be compared nvoCMPOut SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 nviCMPIn1 and nviCMPIn2 are compared OFF is output when...

Page 10: ...valid 0 0 0 Outputs ON or OFF signal of Output 0 or Output 4 depending upon this input nviRROut2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Outputs ON or OFF signal of Output 1 or Output 5 depending upon...

Page 11: ...iables Configuration Properties Extension discrete output Y0 Y2 Y4 Y6 Y8 YA YC YE Output nviDOEX1 status Y1 Y3 Y5 Y7 Y9 YB YD YF Output nviDOEX2 status nv 4 nv 11 nviDOEX1 SNVT_switch nv 12 nv 19 nviD...

Page 12: ...n or off Y1 Y3 Y5 Y7 Y9 YB YD YF of the extension module depending upon this input 100 0 1 ON Other OFF Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS...

Page 13: ...8 XA XC XE X1 X3 X5 X7 X9 XB XD XF Normal Mode Status output at nvoDIEX1 Status output at nvoDIEX2 Combination Mode Refer to the table in the next page fbDIEX SCPTdirection nvoDIEX1 SCPTinvrtOut nvoDI...

Page 14: ...XE X1 X3 X5 X7 X9 XB XD XF nvoDIEX1 nvoDIEX2 OFF OFF 0 0 0 OFF Invalid ON OFF 100 0 1 ON Invalid OFF ON 0 0 0 OFF 0 0 0 OFF ON ON 100 0 1 ON 100 0 1 ON nvoDIEX2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0...

Reviews: