R7F4HC-DC32A-K
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8009-D P. 2 / 7
COMPONENT IDENTIFICATION
Terminator DIP SW
Discrete Output
Status Indicator LED
A20
B20
A1
B1
SW1
Power
Error
RD
1 2 3 4
×10
×1
STATION ADD.
SLD
FE
2
1
DB
3
DG
4
DA
5
NC
NC
4
5
FE1
3
PWR-
2
PWR+
1
Run
SD
Connector for Power Supply
CC-Link Connector
Output Connector
Station Address
Setting Rotary SW
Operation Mode Setting
DIP SW (SW1)
Status Indicator LED
■
TOP VIEW
■
FRONT VIEW
■
STATUS INDICATOR LED
ID
STATUS COLOR FUNCTION
Power
ON
Green
Internal 5V power is in normal
status.
Run
ON
Green
The refresh data is received
normally
Error
ON
Red
The received data is abnormal.
SD
ON
Green
The module is transmitting.
RD
ON
Green
The module is receiving.
■
DISCRETE OUTPUT STATUS INDICATOR LED
Green LED shows the output status.
ON : LED ON
OFF : LED OFF
■
STATION ADDRESS
The left switch determines the tenth place digit, while the
right one does the ones place digit of the station address
(1 - 64).
(Factory setting: 00)
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Station Address Setting (x1)
Station Address Setting (x10)
■
OPERATING MODE
(*) Factory setting
• Read Rate (SW1-1, 1-2, 1-3)
BAUD RATE
SW1
1
2
3
0: 156 kbps (*)
OFF
OFF
OFF
1: 625 kbps
ON
OFF
OFF
2: 2.5 Mbps
OFF
ON
OFF
3: 5 Mbps
ON
ON
OFF
4: 10 Mbps
OFF
OFF
ON
• OUTPUT AT THE LOSS OF COMMUNICATION (SW1-4)
OUTPUT AT THE LOSS OF COMMUNICATION
SW1
4
Output clear (output OFF)
OFF
Hold the output (*)
(maintains the last data received normally)
ON
■
TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate. (Factory setting OFF)