R7F4DC-DAC16C-C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7767-H  P. 2 / 8

COMPONENT IDENTIFICATION

Power

Error

RD

Run

SD

0

8

X

Y

1

9

2

A

3

B

4

C

5

D

6

E

7

F

SW1

  

ON

TERM

ON

×10 SA ×1

I/O Connector

Power Supply / Exc. Supply

Connector

CC-Link Connector

Terminator DIP SW

Status Indicator LED

Station Address
Setting Rotary SW

Discrete I/O Status Indicator LED

Operation Mode Setting
DIP SW (SW1)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

Power

Green

ON when internal 5V power is in normal 
status.

Run

Green

ON when the communication is normal*

1

Error

Red

ON when the received data is abnormal.

SD

Green

ON when the module is transmitting.

RD

Green

ON when the module is receiving.

*1. Run LED turns off when no command is received from the 

master device.

 

DISCRETE I/O STATUS INDICATOR LED

Green LED shows the I/O status.
  ON : LED ON
  OFF : LED OFF

 

STATION ADDRESS

The left switch determines the tenth place digit, while the  
right one does the ones place digit of the station address 
(1 - 64).
(Factory setting: 00)

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

 

OPERATING MODE

(*) Factory setting

• Baud Rate (SW1-1, 1-2, 1-3)

Baud Rate is selected with the DIP switch

BAUD RATE

SW1

1

2

3

156 kbps (*)

OFF

OFF

OFF

625 kbps

ON

OFF

OFF

2.5 Mbps

OFF

ON

OFF

5 Mbps

ON

ON

OFF

10 Mbps

OFF

OFF

ON

• Output at the Loss of Communication (SW1-4)

OUTPUT AT THE LOSS OF COMMUNICATION

SW1

4

Output clear (output OFF)

OFF

Hold the output (*)
(maintains the last data received normally)

ON

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate. (Factory setting OFF)

Summary of Contents for R7F4DC-DAC16C-C

Page 1: ...input and output connected to the unit etc POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating...

Page 2: ...ule is receiving 1 Run LED turns off when no command is received from the master device DISCRETE I O STATUS INDICATOR LED Green LED shows the I O status ON LED ON OFF LED OFF STATION ADDRESS The left...

Page 3: ...t from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF OFF Power input removed or power...

Page 4: ...GY 0 75mm2 Phoenix Contact AI1 10 1 0mm2 Phoenix Contact AI1 5 10 1 5mm2 Phoenix Contact PIN NO ID FUNCTION PIN NO ID FUNCTION X0 1 X0 Input 0 Y8 1 Y8 Output 8 2 24V 24V DC 2 24V 24V DC 3 GND 0V 3 GND...

Page 5: ...from the DIN rail A C B DIN RAIL MOUNTING RIGHT ANGLE Mounting A Insert the longer DIN rail mounter slider until it clicks twice as shown below A B Set the upper hook at the rear side of the unit on...

Page 6: ...a 4 16 deep CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal Detection Circuit DA DG DB SLD FE SN...

Page 7: ...nit mm inch 125 4 92 2 M4 DATA ALLOCATION F 0 1F F 0 1F RX n 0 7 RX n 0 0 Unused RY n 0 F RY n 0 8 Unused Interval timed Response X Refresh Data Y I O DATA DESCRIPTIONS DISCRETE I O 0 15 Input 0 Input...

Page 8: ...6 6659 8510 E mail info m system co jp EM 7767 H P 8 8 COMMUNICATION CABLE WIRING DA DB DG SLD FG DA DB DG SLD FE R7F4DC DA DB DG SLD FE R7F4DC 1 Master module Terminating Resistor blue white yellow 1...

Reviews: