M-system R7E-YV2 Instruction Manual Download Page 5

R7E-YV2

P. 5 / 6

EM-7807-D Rev.4

MODBUS FUNCTION CODES & SUPPORTED CODES

 

Data and Control Functions

CODE

NAME

01

Read Coil Status

X

Digital output from the slave (read/write)

02

Read Input Status

X

Status of digital inputs to the slave (read only)

03

Read Holding Registers

X

General purpose register within the slave (read/write)

04

Read Input Registers

X

Collected data from the field by the slave (read only)

05

Force Single Coil

X

Digital output from the slave (read/write)

06

Preset Single Registers

X

General purpose register within the slave (read/write)

07

Read Exception Status

08

Diagnostics

X

09

Program 484

10

Poll 484

11

Fetch Comm. Event Counter

X

Fetch a status word and an event counter

12

Fetch Comm. Event Log 

X

A status word, an event counter, a message count and a 
field of event bytes

13

Program Controller

14

Poll Controller

15

Force Multiple Coils

X

Digital output from the slave (read/write)

16

Preset Multiple Registers

X

General purpose register within the slave (read/write)

17

Report Slave ID

X

Slave type / ‘RUN’ status

18

Program 884/M84

19

Reset Comm. Link

20

Read General Reference

21

Write General Reference

22

Mask Write 4X Register

23

Read/Write 4X Register

24

Read FIFO Queue

 

Exception Codes

CODE

NAME

01

Illegal Function

X

Function code is not allowable for the slave

02

Illegal Data Address

X

Address is not available within the slave

03

Illegal Data Value

X

Data is not valid for the function

04

Slave Device Failure

05

Acknowledge

06

Slave Device Busy

07

Negative Acknowledge

08

Memory Parity Error

 

Diagnostic Subfunctions

CODE

NAME

00

Return Query Data

X

Loop back test

01

Restart Comm. Option

02

Return Diagnostic Register

03

Change ASCII Input Delimiter

04

Force Listen Only Mode

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7E-YV2

Page 1: ...and confirm its operational range as indicated below 24V DC rating 24V 10 approx 115mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and output signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to co...

Page 2: ... ON ON OFF 0 1V DC ON ON ON OFF 0 5 0 5V DC ON ON ON ON PC Configurator setting Caution SW1 3 is unused Be sure to turn off unused one POWER SUPPLY TERMINAL ASSIGNMENT 4 NC 5 NC 6 24V 1 NC 2 NC 3 FG 7 0V NO ID FUNCTION NOTES 1 NC 2 NC 3 FG FG 4 NC 5 NC 6 24V Power input 24V DC 7 0V Power input 0V OUTPUT TERMINAL ASSIGNMENT 6 NC 7 VH0 8 VL0 1 NC 2 COM0 3 COM0 9 VH1 4 COM1 10 VL1 5 COM1 NO ID FUNCTI...

Page 3: ...IDE SPAN VOLTAGE VHn VLn COMn NARROW SPAN VOLTAGE 7 VH0 8 VL0 2 COM0 3 COM0 OUTPUT 0 9 VH1 10 VL1 4 COM1 5 COM1 OUTPUT 1 7 6 0V 24V DC 3 FG Modbus TCP RJ 45 CONNECTOR EXTENSION CONNECTOR OUTPUT RANGE Wide span voltage 10 10V DC 5 5V DC 0 10V DC 0 5V DC 1 5V DC Narrow span voltage 1 1V DC 0 1V DC 0 5 0 5V DC WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL mm inch Refer to the ...

Page 4: ...from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the connection cannot be established normally due to e g wrong IP address other replies such as timeout will be received CHECK CONNECTION TO THE APPLICATION SOFTWARE Check Poin...

Page 5: ... bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within the slave read write 17 Report Slave ID X Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Reference 21 Write General Reference 22 Mask Write 4X Register 23 Read Write 4X Register 24 Read FIFO Qu...

Page 6: ...d I Integer 1500 11500 15 115 F Floating Note DO NOT access addresses other than mentioned above Such access may cause problems such as inadequate operation STATUS Analog input modules models R7E SV4 R7E TS4 R7E RS4 R7E MS4 R7E CT4E can show input status of each channel Analog output modules models R7E YS2 R7E YV2 and discrete I O modules models R7E DA16 R7E DC16A R7E DC16B shows 0 at the same add...