EM-7802-B Rev.10 P. 3 / 10
PC CONFIGURATOR
The following parameter items can be set with using PC Configurator Software (model: R7CON).
Refer to the users manual for the R7CON for detailed operation of the software program.
■
INTERFACE SETTING
PARAMETER
SETTING RANGE
DEFAULT SETTING
Communication Timeout
0.0 – 3276.7 (sec.)
1.0 (sec.)
Status Data
ON: Disable
OFF: Enable
OFF: Enable
Serial ID
English one-byte characters within 8 characters
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
DEFAULT SETTING
TC Type
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)
K (CA)
Temp Unit
C, F, K
C
Zero scale
-32000 to +32000
0
Full scale
-32000 to +32000
10000
Bias
-320.00 to +320.00
0.00
Gain
-3.2000 to +3.2000
1.0000
Zero temp
Depends on sensor type
0.00 (degC)
Full temp
Depends on sensor type
0.00 (degC)
■
EXTENSION MODULE SETTING
PARAMETER
SETTING RANGE
DEFAULT SETTING
Output Hold/Clear
Output Hold
Output Clear
Output Hold