R7C-SV4

EM-7801-A  Rev.7  P. 2 / 10

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

STATION ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED 

*

1

(B)  Station Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  CC-Link, Power Supply Terminals
(G)  Input Terminals

*

1. Refer to ‘Status Indicator LED’ section for detailed information.

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is sup-
plied normally.

RUN

Red

Turns on when the refresh data is re-
ceived normally.

ERR

Red

Turns on when the received data is 
abnormal.

SD

Red

Turns on when the module is transmit-
ting.

RD

Red

Turns on when the module is receiving.

 

STATION ADDRESS

Station Address is selected between 1 and 64 in decimal.
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps

 

OPERATING MODE

(*) Factory setting

• Extension (SW1-1, 1-2)

SW1-1 SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

• Conversion rate / Accuracy (SW1-3, 1-4)

SW1-3 SW1-4 CONVERSION RATE / ACCURACY

OFF

OFF

80 msec. / ±0.1% (*)

ON

OFF

40 msec. / ±0.2%

OFF

ON

20 msec. / ±0.4%

ON

ON

10 msec. / ±0.8%

• Input range (SW1-5, 1-6, 1-7, 1-8)

SW1-5 SW1-6 SW1-7 SW1-8 INPUT RANGE

OFF

OFF

OFF

OFF

-10 – +10V DC (*)

ON

OFF

OFF

OFF

-5 – +5V DC

OFF

ON

OFF

OFF

-1 – +1V DC

ON

ON

OFF

OFF

0 – 10V DC

OFF

OFF

ON

OFF

0 – 5V DC

ON

OFF

ON

OFF

1 – 5V DC

OFF

ON

ON

OFF

0 – 1V DC

ON

ON

ON

OFF

-0.5 – +0.5V DC

ON

OFF

OFF

ON

-20 – +20mA DC

OFF

ON

OFF

ON

4 – 20mA DC

ON

ON

OFF

ON

0 – 20mA DC

ON

ON

ON

ON

PC Configurator setting

 

POWER SUPPLY, CC-LINK TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

DB

White

2

SLD

Shield

3

FG

FG

4

DA

Blue

5

DG

Yellow

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

VL0

11

I0

12

VL1

1

VH0

2

COM0

3

VH1

13

I1

4

COM1

14

NC

5

NC

15

VL2

6

VH2

16

I2

7

COM2

17

VL3

8

VH3

9

COM3

18

I3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

VH0

Wide span volt. 0 10

VL0

Narrow span volt. 0

2 COM0 Common 0

11

I0

Current range 0

3

VH1

Wide span volt. 1

12

VL1

Narrow span volt. 1

4 COM1 Common 1

13

I1

Current range 1

5

NC

No connection

14

NC

No connection

6

VH2

Wide span volt. 2

15

VL2

Narrow span volt. 2

7 COM2 Common 2

16

I2

Current range 2

8

VH3

Wide span volt. 3 17

VL3

Narrow span volt. 3

9 COM3 Common 3

18

I3

Current range 3

 

INPUT RANGE

• 

Wide span

:  -10 – +10V DC, -5 – +5V DC, 0 – 10V DC,

0 – 5V DC, 1 – 5V DC

• 

Narrow span

: -1 – +1V DC, 0 – 1V DC, -0.5 – +0.5V DC

• 

Current input

:  -20 – +20mA DC, 0 – 20mA DC,

4 – 20mA DC

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7C-SV4

Page 1: ...nstallation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to revi...

Page 2: ...ON Discrete output 8 or 16 points Conversion rate Accuracy SW1 3 1 4 SW1 3 SW1 4 CONVERSION RATE ACCURACY OFF OFF 80 msec 0 1 ON OFF 40 msec 0 2 OFF ON 20 msec 0 4 ON ON 10 msec 0 8 Input range SW1 5...

Page 3: ...ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF OFF Power input removed Or power supply failure OFF...

Page 4: ...OMn WIDE SPAN VOLTAGE VHn VLn In COMn NARROW SPAN VOLTAGE EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor termi...

Page 5: ...ION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval timed Response X Refresh Data Y RX n 0 F to RX n 0 0 Reserved Status RX n...

Page 6: ...Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Input range error 15 115 0 Normal 1 Error ADC error no response from ADC 0 Normal 1 Error STATUS Analog input module without extension mod...

Page 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module...

Page 8: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Page 9: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to t...

Page 10: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To con...