Noise

Filter

Motor
Drive Cable

Maintain distance between
cables and noise sources.

Grounding in pig tail form
is not effective.

• Points of cautions applicable when wiring the R7C Series

To external apparatus

Keep the cable as 
short as possible.

To external apparatus

Shielded

Cable

Earth
Clamp

Remove a part of the shielded

cable cover and ground it 

to the internal panel 

plate using an earth

clamp.

To connect with 

apparatuses outside 
the control panel via 

CC-Link, ground the

cable shield using

an earth clamp.

Keep the wires away from 
each other at both ends of 
the filter.

Summary of Contents for R7C-EC16A

Page 1: ...his equipment must be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instru...

Page 2: ...UNCTION NO ID FUNCTION 1 0V 0V common 10 24V 24V DC 2 Y0 Output 0 11 Y1 Output 1 3 Y2 Output 2 12 Y3 Output 3 4 Y4 Output 4 13 Y5 Output 5 5 Y6 Output 6 14 Y7 Output 7 6 Y8 Output 8 15 Y9 Output 9 7 Y...

Page 3: ...12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 24V Y0 2 Output Connection Example 10 1 2 Y0 0V 24V 18 YF WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing belo...

Page 4: ...ing the R7C Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out...

Page 5: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the co...

Page 6: ...Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from t...

Page 7: ...m is not effective Points of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of...