R6-NP1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7792 Rev.2 P. 4 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
90 (3.54)
5.6
(.22)
90 (3.54)
LOCKING CLAMP
POSITIONING GUIDE
18 (.71)
■
CONNECTION DIAGRAM
INTERNAL POWER
INTERNAL BUS
CONFIGURATION JACK
JACK
BUS CONNECTOR
PROFIBUS
D-SUB CONNECTOR
I/O DATA DESCRIPTIONS
• 16-bit Analog Data
0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Negative values are represented in 2’s complements.
0
15
• Discrete Data
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 4 (Output 4)
Not Used (Remains “0”)
0 : OFF
1 : ON
0
15