background image

COMPONENT IDENTIFICATION

RUN Indicator LED

ERR Indicator LED

Configuration Jack

RJ-45 Connector

■ 

SIDE VIEW

■ 

FRONT VIEW

ON

1 2 3 4 5 6 7 8

LED Function

Data Allocation

LINK
DPLX (Duplex)
COLL (Collision)
LINK10 (10Mbps)
LINK100

(100Mbps)

Ethernet LED

Not used

Not used

8

67

345

2

1

0

F E D C B A

9

8

67

345

2

1

0

F E D C B A

9

 

SIDE DIP SW

(*) Factory setting

• Data Allocation Mode: SW1, SW2 

SW

DATA ALLOCATION MODE

2

1

1

OFF (*)

ON

2

OFF (*)

OFF

• LED Function: SW3

SW3

LED FUNCTION

RUN

ERR

OFF (*) Green when normal

Green ON/blinks in an 
abnormality

ON

Red when receiving

Red when transmitting

Note: Be sure to set unused SW4 through 8 to OFF.

 

ETHERNET INDICATORS

ID

COLOR

FUNCTION

LINK

Red

ON at LINK

DPLX

Red

ON with full-duplex communication

LINK10

Red

ON with 10 Mbps connection

LINK100

Red

ON with 100 Mbps connection

COL

Red

Blinking when collision occurs

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R5CON for detailed operation.

 

NETWORK MODULE SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

3.0 (sec.) 

IP Address

0 – 255

192.168.0.1

Subnet Mask

0 – 255

255.255.255.0

TCP Socket Port 1

0 – 32767

502

TCP Socket Port 2

0 – 32767

502

TCP Socket Port 3

0 – 32767

502

TCP Socket Port 4

0 – 32767

502

Linger 1

0.0 – 3276.7 (sec.)

180.0 (sec.)  

Linger 2

0.0 – 3276.7 (sec.)

180.0 (sec.) 

Linger 3

0.0 – 3276.7 (sec.)

180.0 (sec.) 

Linger 4

0.0 – 3276.7 (sec.)

180.0 (sec.) 

R5-NE1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-6111  Rev.10  P. 2 / 8

Summary of Contents for R5-NE1

Page 1: ...ilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative h...

Page 2: ...ed ON with full duplex communication LINK10 Red ON with 10 Mbps connection LINK100 Red ON with 100 Mbps connection COL Red Blinking when collision occurs PC CONFIGURATOR With configurator software set...

Page 3: ...90 3 54 LOCKING CLAMP POSITIONING GUIDE 18 71 CONNECTION DIAGRAM INTERNAL POWER INTERNAL BUS CONFIGURATION JACK JACK BUS CONNECTOR Modbus TCP RJ 45 CONNECTOR R5 NE1 5 2 55 Minamitsumori Nishinari ku...

Page 4: ...m bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the connection c...

Page 5: ...ithin the slave 17 Report Slave ID Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Reference 21 Write General Reference 22 Mask Write 4X Register 23 Read Write 4X Register...

Page 6: ...T 4 Module 4 Ai 1 INT 16 Module 16 Ai 1 INT 17 18 Module 1 Ai 1 Float 19 20 Module 2 Ai 1 Float 21 22 Module 3 Ai 1 Float 23 24 Module 4 Ai 1 Float 47 48 Module 16 Ai 1 Float Holding Registers 4X 1 Mo...

Page 7: ...en there is an error in one or more channels the bit corresponding to the channels turns to 1 The bit corresponding to unmounted channels turns to 1 DC current output modules check output wire breakdo...

Page 8: ...eger section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Negative values are represented in 2 s complements 0 15 4 POINT DISCRETE DATA models R5 DA4 DC4...

Reviews: