background image

R30US4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9016  Rev.2  P. 6 / 6

PC CONFIGURATOR

The following parameter items can be set with using PC 
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT 
SETTING

Unused setting

CH enabled
CH disabled

CH enabled

Input type

-10 – +10 V DC
-1000 – +1000 mV DC
-20 – +20 mA DC
POT 0 – 4000 Ohm
POT 0 – 2500 Ohm
POT 0 – 1200 Ohm
POT 0 – 600 Ohm
POT 0 – 300 Ohm
POT 0 – 150 Ohm
OHM 0 – 4000 Ohm
RTD Pt 100
RTD Pt 500
RTD Pt 1000
RTD Pt 50 Ω
RTD JPt 100
RTD Ni 508.4 Ω
RTD Cu 10
TC (PR)
TC K
TC E
TC J
TC T
TC B
TC R
TC S
TC C
TC N
TC U
TC L
TC P

-10 – +10 V DC

Wiring

2-wire
3-wire

Burnout

Upscale
Downscale
None

CJC

Enabled
Disabled

Unit

degC
degF
K

Fine zero adjustment -320.00 – +320.00 (%) 0.00 (%)
Fine gain adjustment -3.2000 – +3.2000

1.0000

Zero base

depends on input types*

1

-10.000 V DC

Full base

depends on input types*

1

10.000 V DC

Scaled range Zero

-32 000 – +32 000

0

Scaled range Span

-32 000 – +32 000

10 000

First order lag filter

0.0, 0.5 – 60.0 sec.

0.0 sec.

*1. For details, refer to the users manual of R30CFG. 