background image

MODEL: R30NCIE1

R30NCIE1 SPECIFICATIONS

ES-9020 Rev.6   Page 4/7

https://www.m-system.co.jp/

0

  0

RX(n+0)

Remote READY

Module Status (R30 Series)

Module Status (R3 Series)

Error Status (R30 Series)

Data Error Status (R30 Series)

Error Status (R3 Series)

Data Error Status (R3 Series)

15

  2   1

  A

  B

  C

  D

  E

  3

  F

  9   8   7   6   5   4

RX(n+3)

RX(n+4)

RX(n+5)

RX(n+6)

RX(n+2)

RX(n+1)

RX(n+7)

Unused

•  RX(n+0)0 to 7 is reservation area, RX(n+0) is used as Ready signal, the bit is “1” when this module is in normal.

  RX(n+0)8 to A, RX(n+0)C to F are not used.

•  Module Status

  RX(n+1)0 to RX(n+1)F indicate whether individual I/O modules of R30 series are mounted or not .
  RX(n+2)0 to RX(n+2)F indicate whether individual I/O modules of  R3 series are mounted or not.
  The bit corresponding to the mounted slot turns to “1”, and the unmounted slot to “0”

•  Error Status 

  RX(n+3)0 to RX(n+3)F indicate error status for each module of R30 series.
  The bit corresponding to such module turns to “1”, as described below.
  When the each module is detached, the error bit is cleared.
  However, when the last module is detached, the error bit is held.
    R30X16(under development) input power in error or disconnected.
    R30Y16(under development) output current in error (e.g. load unconnected)
    RX(n+4)0 to RX(n+4)F indicate error status for each module of R3 series.
  The bit corresponding to such module turns to “1”, as described below.
  When the each module is detached, the error bit is held.
    R3-TSx, R3-RSx, R3-US4 Input burnout.
    R3-DA16A input power in error or disconnected
    R3-YSx output current error (e.g load unconnected)
    R3-PC16A external power supply in error or disconnected

•  Data Error Status

  RX(n+5)0 to RX(n+5)F indicate data error status for each module of R30 series.
  The bit corresponding to such module turns to “1”, as described below.
  When the each module is detached, the error bit is cleared.
  However, when the last module is detached, the error bit is held.
    Input value is out of -15% to +115%
    R30TS4, R30RS4, R30USx Input burnout.
  RX(n+6)0 to RX(n+6)F indicate error status for each module of R3 series.
  The bit corresponding to such module turns to “1”, as described below.
  When the each module is detached, the error bit is held.
    Input value is out of -15% to +115%
    In the case of R3-US4 (voltage input) input level out of -10% to +110%.

     

RX(n+1)0, RX(n+3)0, RX(n+5)0 

R30 series slot 1

     

RX(n+1)1, RX(n+3)1, RX(n+5)1 

R30 series slot 2

     

RX(n+1)2, RX(n+3)2, RX(n+5)2 

R30 series slot 3

     

 

 

 

:

     

RX(n+1)F, RX(n+3)F RX(n+5)F 

R30 series slot 16

     

RX(n+2)0, RX(n+4)0, RX(n+6)0 

R3 series extension slot 1 

     

RX(n+2)1, RX(n+4)1, RX(n+6)1 

R3 series extension slot 2 

     

RX(n+2)2, RX(n+4)2, RX(n+6)2 

R3 series extension slot 3

     

 

 

 

:

     

RX(n+2)F, RX(n+4)F, RX(n+6)F 

R3 series extension slot 16

Link devices other than the above are not in use.

Summary of Contents for R30NCIE1

Page 1: ...re model R30CFG PC configurator software model R3CON Downloadable at M System s web site For connecting to PC use commercially available Mini B type USB cable provided by user R3 series I O modules ex...

Page 2: ...30BS Weight 125 g 0 28 lb PERFORMANCE Insulation resistance 100 M with 500 V DC Dielectric strength 1500 V AC 1 minute CC Link IE Field to internal bus or internal power 1500 V AC 1 minute power input...

Page 3: ...R30YN16A 1 R30EBS04 1 R3 SV8 8 2 R3 YV8 8 3 R3 DA32A 2 4 R3 DC32A 2 0 15 RWr n 0 Slot 1 2 4 6 8 10 12 14 Slot 2 Slot 3 Slot 4 INPUT DATA The figure below shows the data sent from the device to the mas...

Page 4: ...tus for each module of R3 series The bit corresponding to such module turns to 1 as described below When the each module is detached the error bit is held R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A i...

Page 5: ...is represented in 2 s complements ANALOG DATA 16 bit data models R30RS4 R30TS4 R30US4 etc 0 15 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted i...

Page 6: ...y data is used for BCD Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits 16 POINT DISCRETE DATA models R30XN16A R30YN...

Page 7: ...ing CN1 and CN2 of RJ 45 connector for CC Link IE Field network there is no restriction for connection order INTERNAL BUS INTERNAL POWER RJ 45 MODULAR JACK RJ 45 MODULAR JACK USB CONNECTOR PC CONFIGUR...

Reviews: