MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
Shows each module’s availability and error status.
0
15
Module 1
Module 2
Module 3
:
Module 16
I/O DATA DESCRIPTIONS
■
OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the
last process values are held until the communication is re-established.
■
ANALOG DATA (16-bit data, models: R30SV4, R30SV2, R30YV4, R30YS4, R30US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
Negative percentage is represented in 2’s complements.
0
15
■
ANALOG DATA (16-bit data, models: R30RS4, R30TS4, R30US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.
0
15
■
ANALOG DATA (16-bit data, models: R30CT4E etc.)
16-bit binary data.
Integer that engineering unit value (A) multiplied by 100 (for CLSE-R5, integer that engineering unit value (A) multiplied
by 1000).
0
15