background image

R3-US4

P. 2 / 2

EM-8449 Rev.1

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 DIMENSIONS  mm (inch) 

WIRING INSTRUCTIONS

 SOLDERLESS TERMINAL  mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  Applicable 

wire size: 0.3 – 0.75 mm

2

3.2 (.13) dia.

4 min.

(.16)

12 (.47) max.

6 max.

(.24)

3 (.12) max.

 CONNECTION DIAGRAM

1

12

14

16

18
19
20

3

5

7

9

10

13

15

17

11

2

6

8

4

POSITIONING

GUIDE

109 (4.29)

20–M3

SCREW

TERMINAL

COVER

6.2

(.24)

130 (5.12)

27.5 (1.08)

CJC SENSOR
(4 CJMs)

■ 

RTD

■ 

POTENTIOMETER

■ 

THEMOCOUPLE

• 

Upscale/no burnout

• 

Downscale burnout

+

+

■ 

DC VOLTAGE

+

-

B

A
B

INPUT CONNECTION

C

B

C

B

A

■ 

TERMINAL NETWORK

C

B

A

2

1

11

4

3

13

6

5

15

8

7

17

A

B
C

A

B
C

A

CJC

Sensor

+

-

C

B

A

CJC

Sensor

11

+

3
2
1

MAX

MIN

+

1

2

INPUT 1

13

3

4

INPUT 2

15

5

6

INPUT 3

17

7

8

INPUT 4

BUS CONNECTOR

INTERNAL

POWER

BUS A

BUS B

*

*

For dual redundant communication.

INPUT 4

INPUT 1 INPUT 2

INPUT 3

comp.wire

comp.wire

Note 1: Remove CJC sensor for RTD or potentiometer input.  The CJC sensor does not affect to DC voltage input.
Note 2: Be sure to eliminate noise as much as possible by e.g. using shielded cables. Ground the signal shield to 
             a most stable earth point in the environment. 
Note 3: The temperature imbalance around the terminal affects greatly the cold junction compensation accuracy. 
             In order to minimize such imbalance, do not expose the input terminals directly to the wind from a cooling fan.