R3-TS4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8362 Rev.5 P. 2 / 4
COMPONENT IDENTIFICATION
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
■
FRONT VIEW
■
SIDE VIEW
ERR LED
RUN LED
Conv.
Rate
Temp.
Unit
Input 2 (SW1)
or
Input 4 (SW2)
T/C
Input 1 (SW1)
or
Input 3 (SW2)
Burnout
Functions
■
STATUS INDICATOR LED
RUN indicator:
Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator:
Bi-color (red/green) LED;
Red with burnout;
Green in normal operating conditions.
■
SIDE DIP SW
(*) Factory setting
• Thermocouple Type: SW1, SW2
INPUT 1 (SW1)
INPUT 2 (SW1)
T/C
INPUT 3 (SW2)
INPUT 4 (SW2)
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF OFF OFF K (CA) (*)
ON OFF OFF OFF ON OFF OFF OFF E (CRC)
OFF ON OFF OFF OFF ON OFF OFF J (IC)
ON ON OFF OFF ON ON OFF OFF T (CC)
OFF OFF ON OFF OFF OFF ON OFF B (RH)
ON OFF ON OFF ON OFF ON OFF R
OFF ON ON OFF OFF ON ON OFF S
ON ON ON OFF ON ON ON OFF C (WRe 5-26)
OFF OFF OFF ON OFF OFF OFF ON N
ON OFF OFF ON ON OFF OFF ON U
OFF ON OFF ON OFF ON OFF ON L
ON ON OFF ON ON ON OFF ON P (Platinel II)
OFF OFF ON ON OFF OFF ON ON (PR)
• Burnout: SW3-1
SW3-1
BURNOUT
OFF
Upscale (*)
ON
Downscale
• Temperature Unit: SW3-2, 3-3
SW3-2
SW3-3
TEMP. UNIT
OFF
OFF
°C (*)
ON
OFF
°F
OFF
ON
K (Absolute Temp)
• Conversion Rate: SW3-4
SW3-4
CONV. RATE
OFF
250 msec. (*)
ON
1 sec.