 STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED; 
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED; 

Red with the input circuit abnormality (AD 
converter response failure);
Green in normal operating conditions.

 SIDE DIP SW

• Input Range

: SW1, SW2 (selectable per 8 channels)

INPUT 1 through INPUT 8 (SW1)

RANGE

INPUT 9 through INPUT 16 (SW2)

1

2

3

4

OFF

OFF

OFF

OFF

-10 –  +10V (*)

ON

OFF

OFF

OFF

-5 – +5V

ON

ON

OFF

OFF

0 – 10V

OFF

OFF

ON

OFF

0 – 5V

ON

OFF

ON

OFF

1 – 5V

• Conversion Rate

: SW3

SW

CONVERSION RATE

100 ms (

*

)

50 ms

20 ms

10 ms

SW3-1

OFF

ON

OFF

ON

SW3-2

OFF

OFF

ON

ON

(*)Factory setting