background image

MODEL: R3-NMW1F

R3-NMW1F SPECIFICATIONS

ES-8286 Rev.0   Page 7/12

http://www.m-system.co.jp/

TRANSMISSION DATA DESCRIPTIONS

The DIP SW located at the side of the module specifi es each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     

Module 1 

 

4

     

Module 2 

 

4

     

Module 3 

 

4

     

Module 4 

 

1

     

Module 5 

 

1

     

Module 6 

 

1

     

Module 7 

 

1

Then the I/O data are assigned as in the table below:

ADDRESS

POSITION

Input Registers (3X)
Holding Registers (4X)

1 – 4,

257 – 264

Slot 1

5 – 8,

265 – 272

Slot 2

9 – 12,

273 – 280

Slot 3

13,

281 – 282

Slot 4

14,

283 – 284

Slot 5

15,

285 – 286

Slot 6

16,

287 – 288

Slot 7

ADDRESS

POSITION

Coil (0X)
Inputs (1X)

1 – 64

Slot 1

65 – 128

Slot 2

129 – 192

Slot 3

193 – 208

Slot 4

209 – 224

Slot 5

225 – 240

Slot 6

241 – 256

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned data 
areas  (Data Allocation Type)  are  allotted  with  the  Data Allocation 
Type ‘1’ and ‘4.’  With ‘8’ and ‘16,’ 64 (4 × 16) are automatically al-
lotted.

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

0

15

Module 1

Module 2

Module 3
      :

Module 16

Shows each module's availability and error status.

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)

0

15

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). 
-15 to 0 % is a negative range represented in 2’s complement.
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.

 

Summary of Contents for R3 Series

Page 1: ...less device as main network Wireless deive incorporates a module conforming to FCC part 15 and can be used within the United States only Modbus RTU gateway function available outputs data received wit...

Page 2: ...in use Transmission configuration Multidrop Gateway funcion in use WIRELESS SPECIFICATIONS Communication Standard IEEE802 15 4g Frequency 900 MHz band 902 928 MHz Max Tx power 20 mW Bandwidth 400 kHz...

Page 3: ...Short address 0000 invalid 0001 to FFFD hexadecimal 4 digits 0000 Network name English one byte characters within 16 characters one byte space _ are usable Blank Encryption key 0000 0 to FFFF F hexad...

Page 4: ...ONNECTIONS SLAVE MODE Tx Rx Tx Rx SG Rx Rx HOST PC DA DB DG SLD FE R3 NMW1F DA DB DG SLD FE R3 NMW1F FG FG TERMINATOR GATEWAY MODE DA DB DG SLD FG SLAVE DEVICE DA DB DG SLD FG SLAVE DEVICE DA DB DG SL...

Page 5: ...s 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter 12 Fetch Comm Event Log 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read wr...

Page 6: ...ted slot to 0 Error Status indicates error status for each module as described below The bit corresponding to such module turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or...

Page 7: ...28 Slot 2 129 192 Slot 3 193 208 Slot 4 209 224 Slot 5 225 240 Slot 6 241 256 Slot 7 For Coil 0X and Inputs 1X addresses 16 times assigned data areas Data Allocation Type are allotted with the Data Al...

Page 8: ...n case of CLSE R5 integer obtained by multiplying unit value A by 1000 ACCUMULATED COUNT DATA 32 bit data models R3 PA2 PA4A WT1 WT4 etc 32 bit binary data is used for accumulated counts and encoder p...

Page 9: ...ASSIGNMENTS unit mm inch 109 4 29 45 1 77 200 7 87 TERMINAL COVER 109 4 29 2500 98 43 Dia 3 12 Dia 1 2 05 Dia 27 1 06 36 1 42 80 3 15 WITH SLEEVE ANTENNA WITH ROOFTOP ANTENNA 19 75 1 2 3 4 5 6 150 5...

Page 10: ...protective conductor terminal FE SLD DG DB DA To Other Modbus Devices 5 Configuration Jack JACK USB CONNECTOR Maintenance Connector ANTENNA CONNECTOR 1 4 RUN RUN RUN CONTACT OUTPUT 2 3 6 FE1 U V POWE...

Page 11: ...TCP and RTU protocol Also Gateway function allows to communicate with slave devices connected in multi drop configuration with wired network using Modbus and RTU protocol Wireless Gateway model WL40E...

Page 12: ...MODEL R3 NMW1F R3 NMW1F SPECIFICATIONS ES 8286 Rev 0 Page 12 12 http www m system co jp Specifications are subject to change without notice...