COMPONENT IDENTIFICATION

1

11
12
13
14
15
16
17
18
19
20

2
3
4
5
6
7
8
9

10

ON

8

7

6

5

4

3

2

1

SW1

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

 FRONT VIEW

 SIDE VIEW

ERR LED

RUN LED

Conv.

Rate

Temp.

Unit

Input 2 (SW1)

  or

Input 4 (SW2)

RTD

Input 1 (SW1)

  or

Input 3 (SW2)

Burnout

Functions

 

STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED; 

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED; 

Red with burnout;
Green in normal operating conditions.

 

SIDE DIP SW

(*) Factory setting

• RTD Type: SW1, SW2

INPUT 1 (SW1)

INPUT 2 (SW1)

RTD

INPUT 3 (SW2)

INPUT 4 (SW2)

1

2

3

4

5

6

7

8

OFF OFF OFF OFF OFF OFF OFF OFF

Pt 100 (*) 
(JIS ’97, IEC)

ON OFF OFF OFF ON OFF OFF OFF

Pt 100 
(JIS ’89)

OFF ON OFF OFF OFF ON OFF OFF

JPt 100
(JIS ’89)

ON ON OFF OFF ON ON OFF OFF

Pt 50Ω
(JIS ’81)

OFF OFF ON OFF OFF OFF ON OFF Ni 100

ON OFF ON OFF ON OFF ON OFF Cu 10 @ 25°C

OFF ON ON OFF OFF ON ON OFF Pt 1000

ON ON ON OFF ON ON ON OFF Ni 508.4Ω

OFF OFF OFF ON OFF OFF OFF ON Cu 50

ON OFF OFF ON ON OFF OFF ON Ni 1000

• Burnout: SW3-1

SW3-1

BURNOUT

OFF

Upscale (*)

ON

Downscale

• Temperature Unit: SW3-2, 3-3

SW3-2

SW3-3

TEMP. UNIT

OFF

OFF

°C (*)

ON

OFF

°F

OFF

ON

K (Absolute Temp)

• Conversion Rate: SW3-4

SW3-4

CONV. RATE

OFF

250 msec. (*)

ON

1 sec.